0 <br /> US7WAN SIR SYSTEM <br /> Monthly Monitoring Report <br /> APRIL, 1994 <br /> Report Date: 05/23/94 <br /> Company name :QUIK STOP MARKETS INC. <br /> Station Name: QUIK STOP MARKET Station # : 76 <br /> Address: 1030 S. OLIVE AVENUE City: STOCKTON State: CA <br /> PART A: <br /> ------------------------------------------------------------------------- <br /> Data <br /> Tank ID: Tank and Lines Status Product: Quality: Dels: Sales <br /> PUL TIGHT PREMIUM GOOD 4633 5337 <br /> RUL TIGHT REGULAR UNZEADRD GOOD 40500 43232 <br /> USTMAN INDUSTRIES INC. is a certified Statistical Inventory Reconciliation <br /> (SIR) release detection vendor. Tank status results for monthly monitoring <br /> are based on parameters specified by the EPA protocol for SIR methods. <br /> PART B: Comments-and Recommendations <br /> PUL No comments. <br /> RUL No comments. <br /> For regulatory compliance in California, a piping integrity test <br /> every 12 months and a tank integrity test every 24 months are <br /> required inassociationwith SIR monthly monitoring. <br />