Laserfiche WebLink
USTMAN SIR SYSTMf <br /> Monthly Monitoring Report <br /> DEC ER, 1993 <br /> Report Date: 01/17/94 <br /> Company name :QUIK STOP MARKETS INC. <br /> Station Name: QUIK STOP MARKET Station # : 76 <br /> Address: 1030 S. OLIVE AVENUE City: STOCKTON State: CA <br /> PART A: <br /> ------------------------------------------------------------------------- <br /> Data <br /> Tank ID: Tank and Lines Status: Product: Quality: Dels: Sales <br /> PUL TIGHT PREMIUM GOOD 7225 4086 <br /> RUL TIGHT REGULAR UNLEADED GOOD 37570 36257 <br /> USTMAN INDUSTRIES INC. is a certified Statistical Inventory Reconciliation <br /> (SIR) release detection vendor. Tank status results for monthly monitoring <br /> are based on parameters specified by the .SPA protocol for SIR methods. <br /> PART B: Comments and Recommendations <br /> O/S listed below represent removals, additions or delivery discrepancies <br /> which were accounted for as part of the SIR analysis. <br /> PUL (12/1/1993 599) <br /> RUL (12/1/1993.' 2580) (1212311993: -1071 <br /> For regulatory compliance in California, a piping integrity test <br /> every 12 months and a tank integrity test every 24 months are <br /> required in association with SIR monthly monitoring. <br />