Laserfiche WebLink
USTMAN SIR SYSTEM <br /> Monthly Monitoring Report <br /> OCTOBER, 1993 <br /> Report Date: 11/22/93 <br /> Company name :QUIK STOP MARKETS INC. <br /> Station Name: QUIK STOP MARKET Station # : 76 <br /> Address: 1030 S. OLIVE AVENUE City: STOCKTON State: CA <br /> PART A: <br /> ------------------------------------------------------------------------- <br /> Data <br /> Tank ID: System Status: Product: Quality: Dels: Sales: <br /> PUL TIGHT PREMIUM GOOD 7120 6379 <br /> RUL INCONCLUSIVE REGULAR UNLEADED GOOD 60790 60550 <br /> USTMAN INDUSTRIES INC. is a certified Statistical Inventory Reconciliation <br /> (SIR) release detection vendor. Tank status results for monthly monitoring <br /> are based on parameters specified by the EPA protocol for SIR methods. <br /> PART B: Comments and Recommendations <br /> PUL No comments. <br /> RUL This system showed a consistent gaining trend for the month, and <br /> thus it is Inconclusive. This trend may be due to 1) a meter <br /> calibration problem, 2) the tank may be taking on water, or 3) <br /> deliveries are recorded in net gallons. Ensure that meters are <br /> properly calibrated, tank is free of water, and deliveries are <br /> recorded in gross gallons. <br /> For regulatory compliance in California, a piping integrity test <br /> every 12 months and a tank integrity test every 24 months are <br /> required in association with SIR monthly monitoring. <br />