Laserfiche WebLink
0 * RECEIVED <br /> WESTERN AMERICA TANK TESTING, INC. JUL 2 5 1991 <br /> 3131 Fairhaven Drive <br /> Bakersfield, <br /> CA 93308 ENVIRONMENTAL LT <br /> . � r <br /> (805) 322-9827 IT/'.JL Vi,al; <br /> ANNUAL 3-STEP RED JACKET LEAK DETECTOR TEST <br /> OWNER QUIK STOP MARKET <br /> LOCATION Sacramento. CA. #76 DATE 06/17/91 <br /> PRODUCT: Regular, Unleaded, Premium Unleaded, Diesel (Circle one) <br /> NOTE: Use separate form for each Tank. <br /> (1) Running Pressure 26 , (2) Shut-Off Pressure 32 <br /> (3) Amount of Product Released thru Bibcock to Zero 12 oz. <br /> (4) With Valve Open--Start STP - List Pressure 0 P. S. I. , <br /> (5) Reduce Flow to Rate of 7 oz. per Minute - List Pressure at this Flow <br /> Rate 8 P. S. I . , <br /> (6) Turn STP Off - Let Pressure drop to zero thru Leak just created - List <br /> time for Gauge to Reach Zero min. 15 sec. , <br /> (7) Turn the STP back on - Keep Leak Rate at Bibcock - List pressure <br /> 8 P. S. I. - Flow Rate at Nozzle 1 . 5 G. P.M. , <br /> (8) Stop Leak with STP still on - Does Leak Detector reset X yes no <br /> If yes - How long to reset min 15 sec. , <br /> (9) Turn STP off - List pressure 20 P. S . I . , <br /> (10) Turn STP back on - List time to reach pressure rise min. 5 sec. <br /> (11) List Pressure 26 P. S . I. , <br /> ( 12) Open Nozzle and List Pressure 24 P. S. I . <br /> SATISFACTORY LEAK DETECTOR X Yes No. <br /> LEAK DETECTOR <br /> Model Red Jacket , Date Code & Serial # <br />