Laserfiche WebLink
Walton Ensineerins 9I63731172 P.02 <br />rAlifornla EdItim: SeptillnDer 1997 <br />Vaporless Manufacturing <br />Vaporless LD 2000 and LD 20003 <br />AUTOMATIC MECHANICAL LINE LEAK OETECTOR <br />Certification: Leak rate of 3.0 9ph with P0=100116 and Pr.A=O%. <br />Leak Threshold: 1 .7 gph. A leak is declared if the output of the measurement system equals or <br />exceeds this thres', ♦ <br />- 1. <br />���-'Ilty: Gasoline, diesel, aviation fuel and solvents. <br />Specification: System tests pressurized fiberglass or steel pipeline$. <br />Tests are conducted at operating pressure. <br />Pipeline Capacity: Maximum of 129 gallons. <br />Waiting Time: None betweetxdispensing and testing. <br />None between delivery and testing. <br />Test Period: Response time is 5 seconds. <br />System Features: Permanent Installation on pipeline. <br />Automatic testing of pipeline - <br />Preset threshold. <br />Single test to determine if pipeline is leaking. <br />L02000 - irestricts ftw to dispenser If leak is declared. <br />LD2000S - pump shutoff if leak is declared. <br />Calibration: System must be checked annuaUy for capabiUty of detecting a line leak <br />of 3.0 gph. <br />Vaporiess Manufacturing Evaluator: Ken Wilcox Associates <br />9234 E. Vail" Rd_ Suite 0 Tel: (816) 443-2494 <br />Pmscoft Valley. AZ 86314 <br />Tel: (602) 775-5191 Oate of Evaluation: 11/19M <br />269 <br />Appeelanot on #ft list is not to be corlstued as an endorsement by any fwWatory awcy nor Is It any guarantee of the pedamiance of <br />the method or equipment Equipment should be InxNAW and ovem*0 In accomoce with aff applioMft tma and m9uM=. <br />