Laserfiche WebLink
San Joaquin County <br /> Environmental Health Department <br /> 1868 East Hazelton Avenue, Stockton, California 95205-6232 <br /> Telephone:(209)468-3420 Fax:(209)468-3433 Web:www.sigov.org/ehd <br /> ,. <br /> ,� <br /> dergiround Stcxa�e �10 Pr'ograr i Ilii l C1 Il' i, r7t <br /> Facility Name: Facility Address: Date: <br /> Nella Oil#427 3300 Waterloo Rd, Stockton December 13, 2016 <br /> UST System Observations <br /> 322 HSC 25281.6(a) Unburied below grade emergency generator system failed to meet exemption status ❑V ❑R ❑COS <br /> 323 HSC 25283.5(a) Unburied below grade UST system failed to meet exemption status ❑V ❑R ❑COS <br /> 324 CCR 2717.1(g) Tampered with red tag ❑V ❑R ❑COS <br /> 325 CCR 2717.1(f) Deposited petroleum into a red tagged UST ❑V ❑R ❑COS <br /> 326 HSC 25299(a)(9) Tampered with or disabled leak detection devices or alarms ❑V ❑R ❑COS <br /> 327 CCR 2631.1 UST system not compatible with the substance stored ❑V ❑R ❑COS <br /> 328 HSC 25298 Failed to comply with temporary closure requirements ❑V ❑R ❑COS <br /> 329 HSC 25298 Failed to comply with permanent closure requirements ❑V ❑R ❑COS <br /> 330 CCR 2636(f)(6) Failure to meet all requirements in lieu of a line leak detector for emergency generator tank system ❑V ❑R ❑COS <br /> Single-Wafted Non-Pre ssurized'Pipritg• <br /> 401 CCR 2636(a)(3) Suction piping not properly sloped or incorrectly located check valve ❑V ❑R ❑COS <br /> 402 CCR 2643(d) Daily monitoring of suction pipe(pre-Jan 1984)not performed ❑V ❑R ❑COS <br /> 403 CCR 2643(d) Triennial 0.1 gph line test for conventional suction piping not performed(pre-January 1984) ❑V ❑R ❑COS <br /> 404 CCR 2643(e) Biennial 0.1 gph test for gravity piping not performed(pre-January 1984) ❑V ❑R ❑COS <br /> ' te., CteC: iQt'dlti4tl r _ <br /> 2010 See below Unlisted Administration/Documentation violation ❑V ❑R ❑COS <br /> 2030 See below Unlisted Operations/Maintenance violation ❑V ❑R ❑COS <br /> 2060 See below Unlisted Design/Construction violation ❑V ❑R ❑COS <br /> ' <br /> S_ MARY OF VIOLATIONS <br /> (CLASS 1:CLASS II,or fvIIIN -Notice to Com ) <br /> Item# Remarks <br /> 309 CCR 2636(f)(1)Monitoring in sump/UDC failed to activate an audible and visual alarm or stop the flow product. <br /> The Bravo box float and chain leak monitoring devices in the#2, 6 and 9 under dispenser containment sumps failed <br /> to stop the flow of product at the dispenser when tested. All monitoring equipment shall be maintained to activate an <br /> audible and visual alarm or stop the flow of product at the dispenser when it detects a leak. The service technician <br /> cleaned the float cups and retested, verifying functionality. Violation resolved during the inspection. <br /> This is a repeat violation, Class ll. <br /> Overall Inspection Comments: <br /> A monitoring system certification and routine inspection were done on this day. The facility does not have staff on <br /> site during all operating hours. Electronic liquid sensor alarms are monitored remotely by office personnel in <br /> Auburn, CA. The technician demonstrated that the alarms are recorded in Auburn by showing a screenshot of the <br /> computer monitor in Auburn with today's test alarms listed. <br /> No follow up by the facility is required. <br /> Page 3 of 4 <br />