Laserfiche WebLink
� <br />` <br />^ TA Gy -NDERGR�UND LEAK DETECTION SYSTEM' - �(V3.i2) ' Page 7 <br />C ' 'RON` . ' '��� � ` . ' ` �� ',` . AUU8001 - Jam 28/ 1980, 06:59 <br />,' <br />� ��_������ ���� ��M 1-1 oc-% F-;`-ue <br />TEST DATE : Jan 28, 1980 <br />START TIME : 06:59:33 <br />CLIENT : CHEVRON <br />LOCATION NAME : CHEVRON <br />LOCATION CODE : 99840 <br />TANK CONFIGURATION : <br />Tandem <br />TANK CONTENTS : <br />SUL/RL <br />TANK NUMBER : <br />01 <br />02 <br />TANK DIAMETER : <br />91 <br />91 in <br />TANK CAPACITY : <br />10000 <br />10000 G <br />TANK MANUFACTURER : <br />TANK MATERIAL : <br />Fibreglass <br />Fibreglass <br />TANK REGISTRATION # : <br />TANK DATE INSTALLED : <br />91/ / <br />91/ / <br />INITIAL DIPPED FUEL LEVEL : <br />59.00 <br />66.00 in <br />INITIAL DIPPED WATER LEVEL : <br />0.00 <br />0.00 in <br />POST PUMPING WATER LEVEL : <br />0.00 <br />0.00 in <br />-�0kKq 1---" -�1 FEE E-� �-I " F"E: 0 4.J1L_-F- <br />TEST INITIAL WATER LEVEL : 0.16 0.17 in <br />TEST FINAL WATER LEVEL : 0.16 0.17 in <br />WATER INGRESS : 0.00 0.00 in <br />BUBBLE SIGNATURES : No No <br />VACU-TECT TEST RESULT : Passed Passed <br />COMMENTS: <br />CONCLUSION: TANKS 1 & 2 ARE TIGHT <br />TEST RATE <br />LINE RESULT PRESSU�'E <br />#1 Passed 50 PSI 0.00 6PH <br />#2 <br />#3 <br />#4 <br />#5 <br />#6 <br />COMMENTS: <br />CONCLUSION: LINES 1A & 2A ARE TIGHT <br />TEST RATE <br />RESULT PRESSURE OF' LOSS <br />Passed 50 PSI 0.00 GPH <br />This test was conducted in accordance with U.S. EPA Rule 40 CFR Parts 280 and 281. <br />LYLED. N\MM0 VACU-TECT(tm) Test Number <br />- -- <br />