Laserfiche WebLink
AEMENT PLAN & UST <br />VAZARDOUS MATERIALMONITORI# PLAN <br />1 0-, <br />DEALER: Guy Dahlenbur <br />BUSINESS NAME: Waterloo Chevron <br />STREET: 4400 Waterloo Rd <br />OWNER: CHEVRON, U.S.A. <br />SAN RAMON, CA 94583-0804 <br />CITY: Stockton , CA ZIP: 95215 <br />STATION No: 99840 <br />SITE PHONE # 209-931-2186 - <br />DUNN & BRADSTREET # 00-138-2555 SIC CODE: 5541 5411 <br />NATURE OF BUSINESS: <br />GASOLINE SALES X AUTO REPAIR_X CAR WASH FOOD MART—.-X— <br />EXISTING <br />ARTX <br />EXISTING UNDERGROUND TANKS ARE AS FOLLOWS: <br />No. of SIZE MATERIAL CONST SPILL OVERFILL <br />TANKS (gal) (STL/FG) (SW/DW) (YIN) (Y/N) <br />SUPER UNLEADED 1 10,000 FG SW <br />REGULAR UNLEADED 1 10,000 FG SW <br />LEADED REGULAR 1 10,000 FG SW <br />DIESEL - 0 <br />WASTE OIL 1 1.000 FG SW <br />PRODUCT LINES: MATERIAL: FG <br />CONSTRUCTION: Single Wall <br />LINE LEAK DETECTION METHOD: ELECTRONIC- X MECHANICAL ' <br />All product lines have line leak detectors capable of detecting a leak of <br />3 gallons or more per hour at 10 lbs. per square inch line pressure <br />within -1 hour; see page one -fora description of the equipment -installed <br />at this location. <br />All product lines are pressurized using a submerged pumping system and <br />are tested annually to assure the --leak detectors are functional.Impact <br />valves are also inspected annually to assure closure. <br />Repair and/or replacement_ of- all _.leak_ detectors .- and- impact-valves_will-be-,..-=-. <br />done annually at the -time of inspection and retested to meet the above <br />test conditions. <br />-- *-This-document--is-to-be-- kept- current and- at-- the-- site.- Revision --S-,---1991 <br />