Laserfiche WebLink
RECEIVED <br /> SWRCB,January 2002 D E C 2 IP4415of <br /> 9. SPILL/OVERFILL CONTAINMENT BOXES <br /> Facili is Not Equipped With Spill/Overfill Containment Boxes❑ <br /> Spill/Overfill Containment Boxes are Present,but were Not Tested❑ <br /> Test Method Developed By: ❑Spill Bucket Manufacturer ❑✓ Industry Standard []Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑Pressure ❑Vacuum ❑Hydrostatic <br /> ❑✓ Other(Specify) inches-1 hr visual test <br /> Test Equipment Used:See attached testing procedures Equipment Resolution: inO.a I h,rm.[x <br /> 714.5" 7 <br /> Spill Box#FB 91 Spill Box#VB 87 Spill Box#VB 91 <br /> rBucketDiameter: 12" 12" 12" <br /> 15" 15.5" 15.5" <br /> Wait time between applying <br /> pressure/vacuum/water and 15 minutes 15 minutes 15 minutes 15 minutes <br /> starting test: <br /> Test Start Time: 10:01 am 10:01 am 10:01 am 10:01 am <br /> Initial Reading(RI): 14 s 1h,mu lWM 14.75 15.25 15 <br /> Test End Time: 11:01 am 11:01 am 11:01 am 11:01am <br /> Final Reading(RF): 14 ^mss +^r—.1 lest 14.75 15.25 mea ^ 15 mn --I^r visual <br /> Test Duration: 1 hr 1 hr 1 hr 1 hr <br /> Change in Reading(RF-RI): 0 0.00 0.00 0 <br /> Pass/Fail Threshold or 0.002 0.002 0.002 0.002 <br /> Criteria: <br /> Test Result: ❑✓ Pass ❑Fail QPass ❑Fail ❑✓ Pass, []Fail [DPass ❑Foil <br /> Comments— (include information on repairs made prior to testing,and recommended follow-up for failed tests) <br />