ENVIRONMENTAL CONSULTANT -
<br />SCOPE OF WORK
<br />THE FOLLOWING SCOPE OF WORK WALL BE PERFORMED BY THE ENVIRONMENTAL
<br />CONSULTANT UNDER A SEPARATE CONTRACT WITH AT&T.
<br />1. ATTEND (1) METHODS O PROCEDURE (MOP) MEETING AT THE SITE PRIOR TO
<br />CONSTRUCTION.
<br />2. TRANSPORT AND DISPOSE O FUEL PIPING IN QUANTITIES SHOWN ON
<br />DRAWIN
<br />GS
<br />RO DIEL NAGRO - SAW AL SPED MORTAZAVI - HYDROLOGUE
<br />4005 PORT CHICAGO H04WAY 2793 E FOOTHILL BLVD.
<br />CA 94520 PASADENA, CA 91107
<br />(925) 298-2103 PHONE (626) 56.5-96M PRONE
<br />(925) 827-20.29 FAX (626) 585- OD46 FAX
<br />(925) 872-6577 CELL (6n)755-1556 CELL
<br />24 HOUR EMERGENCY HOTLINE - FOR AFTER-HOURS ONLY
<br />1. CONTRACTOR MUST NOTIFY ENVIRONMENTAL CONSULTANT AND CUPA AT
<br />LEAST 48 HOURS IN ADVANCE TO SCHEDULE ACTIVITIES.
<br />2. CONTRACTOR MUST PROVIDE A COPY OF THE REMOVAL PERMIT, TANK
<br />INSTALL PERMIT (AS APPLICABLE), TO ENVIRONMENTAL CONSULTANT AT TIME
<br />OF TANK REMOVAL
<br />3. CONTRACTOR MUST ADVISE CONSULTANT OF 11-E MOP OR FORWARD
<br />INFORMATION REGARDING ANY ACCESS CONSTRAINTS FOR TRUCKS
<br />CONTRACTOR SHOULD BE ADVISED OF TIME AND LOCATION CHOSEN FOR MOP
<br />MEETING AT LEAST ONE A WEEK PRIOR TO ITS SCHEDULED TIME.
<br />F:\P,oj,,t\M-N-0-P\OIH\2OOM6 49AR Stockton
<br />U VICINE INP
<br />-wALl DIESEL STORAGE
<br />LINDSAY STREET
<br />• P,
<br />TANK & PIPING
<br />O
<br />Q.
<br />ar
<br />o«
<br />) a
<br />F4 0
<br />IV LINE
<br />IN BASEMENT
<br />-
<br />(E) TUR81N; GENERATIN2
<br />rF.WOR
<br />(E FUS IMPS(TVPFIN
<br />(E) PENTHOUSE
<br />(E) FUEL LIKES ON ROOF
<br />(E) BUILDING
<br />(E) BUILDING
<br />(BASEMENT & 7 STORIES)
<br />CHASE
<br />�0
<br />(BASEMENT & 4 STORIES)
<br />0
<br />Z
<br />(E) 1-1/4. 0 FOS
<br />LIKE IN BASEMENT
<br />-
<br />PROPERTY LINE
<br />•As.�,�y'�
<br />SITE PLAN
<br />01OVERALL
<br />1• : tO-O"
<br />ENVIRONMENTAL CONSULTANT -
<br />SCOPE OF WORK
<br />THE FOLLOWING SCOPE OF WORK WALL BE PERFORMED BY THE ENVIRONMENTAL
<br />CONSULTANT UNDER A SEPARATE CONTRACT WITH AT&T.
<br />1. ATTEND (1) METHODS O PROCEDURE (MOP) MEETING AT THE SITE PRIOR TO
<br />CONSTRUCTION.
<br />2. TRANSPORT AND DISPOSE O FUEL PIPING IN QUANTITIES SHOWN ON
<br />DRAWIN
<br />GS
<br />RO DIEL NAGRO - SAW AL SPED MORTAZAVI - HYDROLOGUE
<br />4005 PORT CHICAGO H04WAY 2793 E FOOTHILL BLVD.
<br />CA 94520 PASADENA, CA 91107
<br />(925) 298-2103 PHONE (626) 56.5-96M PRONE
<br />(925) 827-20.29 FAX (626) 585- OD46 FAX
<br />(925) 872-6577 CELL (6n)755-1556 CELL
<br />24 HOUR EMERGENCY HOTLINE - FOR AFTER-HOURS ONLY
<br />1. CONTRACTOR MUST NOTIFY ENVIRONMENTAL CONSULTANT AND CUPA AT
<br />LEAST 48 HOURS IN ADVANCE TO SCHEDULE ACTIVITIES.
<br />2. CONTRACTOR MUST PROVIDE A COPY OF THE REMOVAL PERMIT, TANK
<br />INSTALL PERMIT (AS APPLICABLE), TO ENVIRONMENTAL CONSULTANT AT TIME
<br />OF TANK REMOVAL
<br />3. CONTRACTOR MUST ADVISE CONSULTANT OF 11-E MOP OR FORWARD
<br />INFORMATION REGARDING ANY ACCESS CONSTRAINTS FOR TRUCKS
<br />CONTRACTOR SHOULD BE ADVISED OF TIME AND LOCATION CHOSEN FOR MOP
<br />MEETING AT LEAST ONE A WEEK PRIOR TO ITS SCHEDULED TIME.
<br />F:\P,oj,,t\M-N-0-P\OIH\2OOM6 49AR Stockton
<br />U VICINE INP
<br />COORDINAIM
<br />1. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION OF ALL
<br />WORK.
<br />2. THE GENERAL CONTRACTOR SHALL RESOLVE DIFFERENCES OR DISPUTES
<br />CONCERNING COORDMWTIO N, INTERFERENCE, OR EXTENT OF WORK.
<br />3. USE LARGE-SCALE LAYOUT DRAWINGS OF OTHER AFFECTED WORK, TO
<br />CHECK, COORDINATE AND INTEGRATE THE WORK TO PREVENT
<br />INTERFERENCES
<br />4. COORDINATE WORK PERFORMED BY AT&T AND OTHERS AS R INVOLVES THE
<br />EXECUTION OF THIS WORK.
<br />5, COORDINATE DELIVERY AND STORAGE OF AT&T FURNISHED EQUIPMENT AND
<br />FUEL FOR TESTING.
<br />CUTTING AND PATCHING:
<br />1. PATCHING SHALL SUCCESSFULLY DUPLICATE UNDISTURBED ADJACENT FINISHES,
<br />COLORS, TEXTURES AND PROFILES.
<br />2. COMPLY WITH ALL LOCAL ORDINANCES AND CAL -OSHA REGULATIONS FOR
<br />INDUSTRIAL SAFETY. DO NOT CUT OR ALTER STRUCTURAL MEMBERS WITHOUT
<br />PRIOR WRITTEN APPROVAL OF AT&T.
<br />3. PERFORM CUTTING, ASSOCIATED STRUCTURAL REINFORCING AND PATCHING IN
<br />A MANNER TO PREVENT DAMAGE TO OTHER WORK AND TO PROVIDE PROPER
<br />SURFACES FOR THE INSTALLATION OF MATERIALS, EQUIPMENT AND REPAIRS,
<br />PERFORM DEMOLITION WORK IN SUCH MANNER AS TO PREVENT DAMAGE TO
<br />EXISTING FACILITIES TO REMAIN OR TO BE SALVAGED, AND TO PREVENT
<br />INJURY TO PUBLIC AND WORKERS ENGAGED ON SITE UNDER THIS OR OTHER
<br />CONTRACTS. DEMOLITION DEBRIS SHALL NOT BE MOWED TO ACCUMULATE ON
<br />SITE. HAZARDOUS WORK SHALL NOT BE LEFT STANDING OR FLANGING
<br />OVERNIGHT OR WEEKENDS.
<br />4. WHEREVER CUTTING AND REMOVAL OF PORTIONS OF EXISTING WORK 15
<br />INDICATED, SUCH WORK SMALL BE CUT IN A MANNER THAT WALL PRODUCE
<br />NEAT AND STRAIGHT LINES, PARALLEL TO ADJACENT SURFACES OR PLUMB
<br />FOR VERTICAL SURFACES. GRIND SMOOTH RESULTING EDGES OF CONCRETE
<br />SLABS OR WALKS.
<br />5. NEATLY REMOVE EXISTING FINISH MATERIALS BACK 70 CLEAN STRAIGHT LINE
<br />ON NEAREST SUPPORT IN ORDER TO FACILITATE INSTALLATION O NEW
<br />MATERIALS, PATCHES OR REPAIRS. EXECUTE CUTTING AND DEMOLITION BY
<br />METHODS WHICH WILL PREVENT DAMAGE TO OTHER WORK AND WHICH WILL
<br />PROVIDE PROPER SURFACES TO RECEIVE INSTALLATION OF REPAIRS AND NEW
<br />WORK.
<br />6. KEEP AREAWAYS, WALKS, CORRIDORS AND STREETS FREE OF ORT AND
<br />RUBBISH.
<br />7. REPAIR OR REPLACE IMPROVEMENTS DAMAGED AS A RESULT OF THIS WORK
<br />AT NO ADDITIONAL EXPENSE TO AT&T.
<br />S. PROVIDE WATER DAMS AND OTHER CONTAINMENT PROCEDURES, AS
<br />NECESSARY, FOR CONTROLLING WATER USED FOR CONCRETE SAW CUTTING.
<br />PIPING INSTALLATION NOTES
<br />1. ALL FUEL OL SUPPLY, RETURN AND VENT PIPING SHALL BE INSTALLED
<br />ABOVEGROUND (AS PRACTICAL).
<br />2. ABOVEGROUND FUEL OL SUPPLY, RETURN AND VENT PIPING SHALL BE ASTM
<br />A53 SCHEDULE 40 DOMESTIC (NORTH AMERICA) BLACK STEEL PIPE WITH
<br />THREADED OR WELDED ,DINTS
<br />3. ABOVEGROUND INTERIOR FUEL OL SUPPLY AND RETURN PIPING INSTALLED
<br />IN AREAS WITHOUT CONTAINMENT SHALL BE INSTALLED WITH MONITORED
<br />SECONDARY CONTAINMENT.
<br />4. PROVIDE ADEQUATE PIPE SUPPORTS WHERE REWIRED.
<br />5. INSTALL ALL PIPING THAT IS NOT SECONDARILY CONTAINED IN A MANNER
<br />THAT WILL ALLOW VISUAL INSPECTION OF THE ENTIRE PIPING SYSTEM
<br />INCLUDING TOP, SIDES AND BOTTOM. CHECK WITH AUTHORITY HAVING
<br />JURISDICTION FOR CLEARANCE REQUIREMENTS
<br />6. ALL EXPOSED PIPING SHALL BE MARKED AT INTERVALS NO GREATER THAN
<br />EVERY TWENTY (20) FEET YOUTH PRODUCT COLOR -CODED DIRECTIONAL FLOW
<br />ARROWS, LINES SHALL RE MARKED AT EACH CHANGE IN DIRECTION AND
<br />WHERE WALL, CEILING, OR FLOOR PENETRATIONS OCCUR. IF LINES ARE
<br />SHORTER THAN TWENTY (20) FEET, MARKINGS SHALL APPEAR AT LEAST
<br />ONCE ALONG THEIR LENGTH.
<br />7. GALVANIZED PPE OR FITTINGS SHALL NOT BE USED FOR DIESEL SERVICE.
<br />8. SCOTCH KOTE ABOVEGROUND STEEL PIPING.
<br />NOTE PERSUANT TO STOCCTON FIRE DEPARTMENT REQUEST; ALL PIPE WELDING
<br />IS TO BE INSPECTED AND APPROVED BY A THIRD PARTY WELDING EVALUATOR.
<br />ACCEPTABLE THIRD PARTY WELDING EVALUATORS ARE OSTEO AT THE FOLLOWING
<br />WEBSITE: Mt4://rww.innnnl'rIe-oro/FobrkAta Ineoeetimi Prmram A.html
<br />1. APPROVED PAY SNAIL BE RESPONSIBLE FOR ALL NOTIFICATIONS AND
<br />SCHEDULING IN CONNECTION WITH PETROLEUM STORAGE TANK
<br />REQUIREMENTS AND SHALL MAINTAIN A SITE SPECIFIC SITE SAFETY PLAN
<br />DURING ALL WORK ACTIVITIES.
<br />2. CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, EOUIPMENT AND
<br />SERVICES NECESSARY FOR THE SATISFACTORY COMPLETION OF ALL WORK
<br />CALLED FOR OR REQUIRED BY THE CONTRACT DOCUMENTS.
<br />3. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE OF FOLLOWING:
<br />A LOCAL, STATE AND FEDERAL ABOVEGROUND STORAGE TANK REGULATIONS.
<br />8. ADOPTED FIRE CODE.
<br />C. CAL -OSHA REGULATIONS.
<br />D. ADOPTED NATIONAL ELECTRIC CODE.
<br />E. ALL CRY, COUNTY, AND STATE LAWS AND ORDINANCES.
<br />F. PEI RP200 AS THE INDUSTRY STANDARD FOR INSTALLATION OF
<br />ABOVEGROUND PETROLEUM STORAGE TANKS.
<br />4. CONTRACTOR SHALL PROTECT ALL EXISTING FACILITIES TO REMAIN UNLESS
<br />NOTED OTHERWISE. CONTRACTOR SHALL REPAIR OR REPLACE ANY EXISTING
<br />FACILITIES WHICH ARE DAMAGED BY THE CONTRACTOR'S OPERATIONS TO THE
<br />SATISFACTION OF AT&T.
<br />5. IT SHALL BE THE GENERAL CONT'RACTOR'S RESPONSIBILITY TO DETERMINE
<br />THE EXACT LOCATION(S) AND/OR EXISTENCE OF ALL UNDER -GROUND
<br />UTILITIES IN WORK AREA PR TO CONSTRUCTION WITH A PRIVATE UTILITY
<br />LOCATOR.
<br />6. STANTEC ARCHITECTURE INC.. UNLESS OTHERWISE DETERMINED, SHALL APPLY
<br />AND PAY FOR ALL PERMITS REQUIRED FINK THE COMPLETION OF THIS
<br />PROJECT. CONTRACTOR TO SUPPLY CERTIFICATE O INSURANCE, CITY
<br />BUSINESS LICENSE, EVIDENCE OF CONTRACTORS UCENSE AND ANY OTHER
<br />ID'ORMATION WHICH THE PERMITTING AGENCY REWIRES FROM
<br />CONTRACTORS.
<br />7. GENERAL CONTRACTOR SHALL L NOTIFY THE ENGINEER PROMPTLY IF SITE
<br />CONDITIONS OR DIMENSIONS DISAGREE WITH INFORMATION SHOO ON THESE
<br />DRAWINGS. WORK IS NOT TO PROCEED LWM SUCH DIFFERENCES ARE
<br />RESOLVED.
<br />8, GENERAL CONTRACTOR SHALL PROVIDE A DETAKZD METHOD OF PROCEDURE
<br />M.O.P.) TO AT&T FOR APPROVAL PRIOR TO START OF CONSTRUCTION. MOP
<br />INCLUDE BUILDING VENTILATION SAFETY PROCEDURES.
<br />9. GENERAL CONTRACTOR SHALL SUPPLY AT&T WITH A DETAILED WORK
<br />SCHEDULE MID UPDATE PROGRESS AND/OR CHANGES ON A WEEKLY BASIS.
<br />10. APPROVED PAV SHALL PROVIDE THREE SETS O SUBMITTALS ON ALL
<br />EQUIPMENT TO THE ENGINEER PRIOR TO START OF CONSTRUCTION.
<br />11. ALL ELECTRICAL WORK TO BE DONE IN COMPLIANCE WITH CHAPTER 5,
<br />ARTICLES 500-50 AND 514 OF TNR' NATIONALELECTRIC COIF. SEAT ALL
<br />CONDUITS AS REWIRED UNDER THE CODE.
<br />12. APPROVED PAV SHALL SUPPLY FIVE COMPLETE SETS OF OPERATION,
<br />MAINTENANCE AND TEST DATA TO GENERAL CONTRACTOR. OPERATIONAL,
<br />MAINTENANCE AND TEST DATA SHALL INCLUDE ALL THE ITEMS LISTED ON
<br />SHEET F7 - PROJECT CLOSE-OUT DOCUMENTS AND CHECKLISTS. ALL
<br />DOCUMENTS TO BE IN ACCORDANCE WITH CURRENT AT&T EMS 200 SERIES
<br />PRACMES MW CHECKLISTS FOR REGULATORY BINDERS AND ON-SITE
<br />BINDERS.
<br />13. NEW TANKS AND PIPING SHALL BE TESTED IN ACCORDANCE WITH
<br />APPLICABLE REGULATIONS AND SPECIFICATIONS.
<br />14. THE GENERAL CONTRACTOR SHALL COMPLY WITH ALL DUST CONTROL
<br />REQUIREMENTS AS SET FORTH BY THE FACILITY SUPERVISOR OR HIS
<br />DESIGNATED REPRESENTAINE WHEN DRILLING, CORING. OR OTHERWISE
<br />MAKING HOLES OR PENETRATIONS INSIDE THE FACILITY BUILDING,
<br />INCLUDING SCREW HOLES FOR CONDUIT SUPPORTS. ETC. AS A MINIMUM
<br />EFFORT. THE CONTRACTOR SMALL CONTAIN AND COLLECT ALL DUST BY
<br />MEANS OF PLASTY SHEET ISOLATION OF THE WORK AREA AND VACUUMING
<br />THE DUST AS IT OCCURS.
<br />15. NO WORK SHALL BE PERFORMED OVER TELLPHDME SWITCH EQUIPMENT
<br />WITHOUT A MOP (METHOD OF PROCEDURE).
<br />16. AT&T ENDS SHALL PERFORM 6 MONTH COMPLIANCE TESTING. ANY FAILURES
<br />ARE THE RESPONSIBILITY OF THE INSTALLATION CONTRACTOR.
<br />17. PROVIDE MONITORING FOR EACH DAY TRIC THAT HAS A CAPACITY OF 100
<br />GALLONS OR MORE. REFER TO THE TANK /LEAK DETECTION
<br />SYSTEM ALARM SUMMARY FOR MONITORING REQUIREMENTS. ASSURE ALL
<br />SENSORS MEET CALIFORNIA STATE WATER RESOURCES CONTROL BOARD'S
<br />0RCB) MOST RECENT REOOREMENTS FOR EACH APPLICATION AS
<br />UNED IN SWRCB LETTER L0111
<br />18, PRIOR TO DISCONNECTING THE VEEDER ROOT ILS -350 MONITORING SYSTEM
<br />FOR ANY REASON, CONTRACTORS MUST NOTIFY THE CAM (CALIFORNIA
<br />ALARMS MANAGER) MO RECEIVE WRITTEN CONFIRMATION 48 HOURS IN
<br />ADVANCE OF ACTIVITY. CONTRACTORS MUST CONTACT THE CAM BY CALLING
<br />1-800-KNOW-EHS. THE DISCONNECT/MODIFCATON MUST BE DONE BY A
<br />VEEDER ROOT CERTIFIED LEVEL 4 TEC
<br />FINICIAN.
<br />19. CONTRACTOR SHALL CONTACT THE CALIFORNIA PERMIT MANAGER (CPM) AT
<br />1 -800 -KNOW -EIS SEVEN DAYS PRIOR TO INSTATING, RELOCATING OR
<br />REMOVING AND PORTION OR COMPONENTS ON THE MONITORING SYSTEM IN
<br />ANY CALIFORNIA UST FACILITY.
<br />29. TAUT &AWWAMEWAL SERMICE (TIES) MILL PIERFORm ALL COMPLIANCE TESTING
<br />FOR DSC PST SYSTEM PROJECTS WHRCH NCLIAffiSALLNOTPICATIONS.
<br />DOCUMMTAYMN, CERTIFICATIONS AND REPORTINGAS REQUYIEDRY THELOCAL
<br />AGENCY. TIE PAV M TO EXCLUDE ANY/ALL COSTS FOR COIVPUANCE TESTING AWN
<br />THEIR BIDS. THE GCAPAV WSl COAIV IN WWII THE LOCAL AGENCY WHAT TESTING ✓8
<br />AND INFORM TES. TES WILL PRDVME THE GCA PROPOSAL FOR SITE SPECIRC
<br />COA6PLJANCE TESTING, CONTRACT WITH 714E GC AND BILL THE GC FOR SERVICES.
<br />THE GC AND PAVMW.L COORDIATEWITH TES FORS OF THE TESTS.
<br />21. CONTRACTOR SHALL VERIFY EXACT TANK DIMENSIONS AND SIZE TANK SLAB
<br />PER MANUFACTURER'S WARRANTY AND STRUCTURAL DRAWINGS.
<br />22. IF ANY OF THE REQUIRE) COMPLIANCE TESTING HAS TO BE RESCHEOULED
<br />DDE TO A FARM TEST OR INCOMPLETE WADE¢ THE TANK CONTRACTOR
<br />WILL BE SOLELY MABLE FOR ANY AODITMNAL AND TESTING
<br />COSTS. ALL POTROLEUM STORAGE TANK SYSTEM WORK RELATED 70
<br />compLmmeE TESTING MUST 8E 400% COMPLETS, FUNCTIONAL AND
<br />READY FOR TESTING AND CERTIRCAT/OM (ML - ALL WIRING
<br />CONNECTIONS MADS, MNIT PROGRAMMED AND END-704DW
<br />COMNEC7WMVENFICA71ONS MADE LINES TORE GAIGC CHECKED,
<br />ISOLATED AND CAPPED/ BULKHEAD FITTINOS SECURE, CONTAINMENT
<br />80078 IN PLACE -ETC).
<br />Ft COVER SHEET AND NOTES
<br />F2 PIPING MODPICATION PLAN & NOTES
<br />F3 FUEL PIPING DETAILS
<br />F4 PROJECT CLOSE-OUT DOCUMENTS B CHECKLISTS
<br />ABBREVIATIONS:
<br />(E) EXISTING
<br />(N) NEW
<br />AM AUTHORITY HAVING JURISDICTION
<br />M ALLIANCE ARCHITECT
<br />AST ABOVEGROUND STORAGE TANK
<br />CMM CAUFORNM ALARM MANAGER
<br />CAPSEM CALIFORNIA PETROLEUM STORAGE TANK MANAGER
<br />CEC CALIFORNIA ENVIRONMENTAL CONSULTANT
<br />CPM CALIFORNIA PERMIT MANAGER
<br />CTM CALIFORNIA TESTING MANAGER
<br />DA DESIGN ARCHITECT
<br />WPM DESIGN AND CONSTRUCTION PROJECT MANAGER
<br />EAMC EMERGENCY ALARM MANAGEMENT CENTER
<br />EH&S ENVIRONMENT, HEALTH AND SAFETY
<br />EHSGC ENVIRONMENT, HEALTH. & SAFETY CONTROL CENTER
<br />ESM ENVIRONMENTAL SITE MANAGER
<br />ELD ENHANCED LEAK DETECTION
<br />FOR FUEL OL RETURN
<br />FOS FUEL OIL SUPPLY
<br />FOV FUEL OL VENT
<br />FRP FIBERGLASS REINFORCED PLASTIC
<br />GNFO GLOBAL. NETWORK FIELD OPERATOR
<br />LA LOCAL AUTHORITY
<br />NEC NATIONAL ELECTRIC CODE
<br />NFTS NATIONAL FUEL TANK SUPPORT
<br />NOC NETWORK OPERATIONS CENTER
<br />PAV PETROLEUM APPROVED VENDOR
<br />PST PETROLEUM STORAGE TANK
<br />PSTC PETROLEUM STORAGE TANK CONTRACTOR
<br />RA REVIEW AGENT
<br />U.G. UNDERGROUND
<br />USA UNDERGROUND SERVICE ALERT
<br />USI UNDERGROUND STORAGE TANK
<br />S" OBIM
<br />ENGINEERS, INC.
<br />�5 soin Ute sh®e:
<br />Sen /�, CA 95112-2218
<br />996 14th Street. Site 200 -
<br />WkN ' G 94612-2'25
<br />99 6 Poem Street
<br />y Monterey, CA 93M-1410(408) 282-1500
<br />PAY: (406) 8Y/-2.
<br />wwnsetmohrkn.rom
<br />REVISIONS AUTHORIZATIONS
<br />NT. 621E DATE BY
<br />ISSUE MR CUDIT ROVER (8D* 10/1/10 CS
<br />RESPONSE TO CLEW REVIEW (BOB) 11/1/10 CS
<br />FIRE DEPART" SUBMITTAL 3/15/11 CS
<br />C UPA SMMIITAL 4/07/11 CS
<br />PROPRIETARY AT&T INFORMATION
<br />NOT FOR ODI ML USE DA DOMMME OUTS O AT&T. TIS WOMAKDON INY
<br />ONLY E USED BY AUTHMZED PEBSOMMEL O THE LOCAL MOMENT AGM
<br />W COWWIDN WITH APRCAT01 FOR PERMITS AM NJ HM706 MR BUILDINGS
<br />AtB/ OR ZONES OWIGM
<br />DWINOS P. . a, FOR
<br />4' CORPORATE
<br />REALESTATE
<br />ABOVEGROUND
<br />FUEL PIPING MODIFICATIONS
<br />FOR STANDBY GENERATOR SYSTEM
<br />345 N. SAN JOAQUIN STREET
<br />STOCKTON,CA
<br />SKTNCA01 UE042
<br />SHEET TOLE:
<br />COVER SIFT
<br />AND NOTES
<br />PROJECT i - I CONSULTANT PROM $ 2007680049
<br />DATE 09/30/10 SCALE: AS NGIED
<br />- DRAWN BY: D6 DECKED BY: CBS
<br />AT&T 7mT: 1 OF: 4 SHEETS SHEET NO.
<br />BM Td 707.765.1660 AT&T NO-
<br />�j1
<br />Oft „37 U.S-IFGc 707.765.9008 - 1
<br />P9tdiR- CA A94954', -'-L
<br />94954 mvstwft 9m ROD SATRE 1
<br />wA
<br />• P,
<br />1
<br />aa
<br />ar
<br />o«
<br />) a
<br />COORDINAIM
<br />1. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION OF ALL
<br />WORK.
<br />2. THE GENERAL CONTRACTOR SHALL RESOLVE DIFFERENCES OR DISPUTES
<br />CONCERNING COORDMWTIO N, INTERFERENCE, OR EXTENT OF WORK.
<br />3. USE LARGE-SCALE LAYOUT DRAWINGS OF OTHER AFFECTED WORK, TO
<br />CHECK, COORDINATE AND INTEGRATE THE WORK TO PREVENT
<br />INTERFERENCES
<br />4. COORDINATE WORK PERFORMED BY AT&T AND OTHERS AS R INVOLVES THE
<br />EXECUTION OF THIS WORK.
<br />5, COORDINATE DELIVERY AND STORAGE OF AT&T FURNISHED EQUIPMENT AND
<br />FUEL FOR TESTING.
<br />CUTTING AND PATCHING:
<br />1. PATCHING SHALL SUCCESSFULLY DUPLICATE UNDISTURBED ADJACENT FINISHES,
<br />COLORS, TEXTURES AND PROFILES.
<br />2. COMPLY WITH ALL LOCAL ORDINANCES AND CAL -OSHA REGULATIONS FOR
<br />INDUSTRIAL SAFETY. DO NOT CUT OR ALTER STRUCTURAL MEMBERS WITHOUT
<br />PRIOR WRITTEN APPROVAL OF AT&T.
<br />3. PERFORM CUTTING, ASSOCIATED STRUCTURAL REINFORCING AND PATCHING IN
<br />A MANNER TO PREVENT DAMAGE TO OTHER WORK AND TO PROVIDE PROPER
<br />SURFACES FOR THE INSTALLATION OF MATERIALS, EQUIPMENT AND REPAIRS,
<br />PERFORM DEMOLITION WORK IN SUCH MANNER AS TO PREVENT DAMAGE TO
<br />EXISTING FACILITIES TO REMAIN OR TO BE SALVAGED, AND TO PREVENT
<br />INJURY TO PUBLIC AND WORKERS ENGAGED ON SITE UNDER THIS OR OTHER
<br />CONTRACTS. DEMOLITION DEBRIS SHALL NOT BE MOWED TO ACCUMULATE ON
<br />SITE. HAZARDOUS WORK SHALL NOT BE LEFT STANDING OR FLANGING
<br />OVERNIGHT OR WEEKENDS.
<br />4. WHEREVER CUTTING AND REMOVAL OF PORTIONS OF EXISTING WORK 15
<br />INDICATED, SUCH WORK SMALL BE CUT IN A MANNER THAT WALL PRODUCE
<br />NEAT AND STRAIGHT LINES, PARALLEL TO ADJACENT SURFACES OR PLUMB
<br />FOR VERTICAL SURFACES. GRIND SMOOTH RESULTING EDGES OF CONCRETE
<br />SLABS OR WALKS.
<br />5. NEATLY REMOVE EXISTING FINISH MATERIALS BACK 70 CLEAN STRAIGHT LINE
<br />ON NEAREST SUPPORT IN ORDER TO FACILITATE INSTALLATION O NEW
<br />MATERIALS, PATCHES OR REPAIRS. EXECUTE CUTTING AND DEMOLITION BY
<br />METHODS WHICH WILL PREVENT DAMAGE TO OTHER WORK AND WHICH WILL
<br />PROVIDE PROPER SURFACES TO RECEIVE INSTALLATION OF REPAIRS AND NEW
<br />WORK.
<br />6. KEEP AREAWAYS, WALKS, CORRIDORS AND STREETS FREE OF ORT AND
<br />RUBBISH.
<br />7. REPAIR OR REPLACE IMPROVEMENTS DAMAGED AS A RESULT OF THIS WORK
<br />AT NO ADDITIONAL EXPENSE TO AT&T.
<br />S. PROVIDE WATER DAMS AND OTHER CONTAINMENT PROCEDURES, AS
<br />NECESSARY, FOR CONTROLLING WATER USED FOR CONCRETE SAW CUTTING.
<br />PIPING INSTALLATION NOTES
<br />1. ALL FUEL OL SUPPLY, RETURN AND VENT PIPING SHALL BE INSTALLED
<br />ABOVEGROUND (AS PRACTICAL).
<br />2. ABOVEGROUND FUEL OL SUPPLY, RETURN AND VENT PIPING SHALL BE ASTM
<br />A53 SCHEDULE 40 DOMESTIC (NORTH AMERICA) BLACK STEEL PIPE WITH
<br />THREADED OR WELDED ,DINTS
<br />3. ABOVEGROUND INTERIOR FUEL OL SUPPLY AND RETURN PIPING INSTALLED
<br />IN AREAS WITHOUT CONTAINMENT SHALL BE INSTALLED WITH MONITORED
<br />SECONDARY CONTAINMENT.
<br />4. PROVIDE ADEQUATE PIPE SUPPORTS WHERE REWIRED.
<br />5. INSTALL ALL PIPING THAT IS NOT SECONDARILY CONTAINED IN A MANNER
<br />THAT WILL ALLOW VISUAL INSPECTION OF THE ENTIRE PIPING SYSTEM
<br />INCLUDING TOP, SIDES AND BOTTOM. CHECK WITH AUTHORITY HAVING
<br />JURISDICTION FOR CLEARANCE REQUIREMENTS
<br />6. ALL EXPOSED PIPING SHALL BE MARKED AT INTERVALS NO GREATER THAN
<br />EVERY TWENTY (20) FEET YOUTH PRODUCT COLOR -CODED DIRECTIONAL FLOW
<br />ARROWS, LINES SHALL RE MARKED AT EACH CHANGE IN DIRECTION AND
<br />WHERE WALL, CEILING, OR FLOOR PENETRATIONS OCCUR. IF LINES ARE
<br />SHORTER THAN TWENTY (20) FEET, MARKINGS SHALL APPEAR AT LEAST
<br />ONCE ALONG THEIR LENGTH.
<br />7. GALVANIZED PPE OR FITTINGS SHALL NOT BE USED FOR DIESEL SERVICE.
<br />8. SCOTCH KOTE ABOVEGROUND STEEL PIPING.
<br />NOTE PERSUANT TO STOCCTON FIRE DEPARTMENT REQUEST; ALL PIPE WELDING
<br />IS TO BE INSPECTED AND APPROVED BY A THIRD PARTY WELDING EVALUATOR.
<br />ACCEPTABLE THIRD PARTY WELDING EVALUATORS ARE OSTEO AT THE FOLLOWING
<br />WEBSITE: Mt4://rww.innnnl'rIe-oro/FobrkAta Ineoeetimi Prmram A.html
<br />1. APPROVED PAY SNAIL BE RESPONSIBLE FOR ALL NOTIFICATIONS AND
<br />SCHEDULING IN CONNECTION WITH PETROLEUM STORAGE TANK
<br />REQUIREMENTS AND SHALL MAINTAIN A SITE SPECIFIC SITE SAFETY PLAN
<br />DURING ALL WORK ACTIVITIES.
<br />2. CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, EOUIPMENT AND
<br />SERVICES NECESSARY FOR THE SATISFACTORY COMPLETION OF ALL WORK
<br />CALLED FOR OR REQUIRED BY THE CONTRACT DOCUMENTS.
<br />3. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE OF FOLLOWING:
<br />A LOCAL, STATE AND FEDERAL ABOVEGROUND STORAGE TANK REGULATIONS.
<br />8. ADOPTED FIRE CODE.
<br />C. CAL -OSHA REGULATIONS.
<br />D. ADOPTED NATIONAL ELECTRIC CODE.
<br />E. ALL CRY, COUNTY, AND STATE LAWS AND ORDINANCES.
<br />F. PEI RP200 AS THE INDUSTRY STANDARD FOR INSTALLATION OF
<br />ABOVEGROUND PETROLEUM STORAGE TANKS.
<br />4. CONTRACTOR SHALL PROTECT ALL EXISTING FACILITIES TO REMAIN UNLESS
<br />NOTED OTHERWISE. CONTRACTOR SHALL REPAIR OR REPLACE ANY EXISTING
<br />FACILITIES WHICH ARE DAMAGED BY THE CONTRACTOR'S OPERATIONS TO THE
<br />SATISFACTION OF AT&T.
<br />5. IT SHALL BE THE GENERAL CONT'RACTOR'S RESPONSIBILITY TO DETERMINE
<br />THE EXACT LOCATION(S) AND/OR EXISTENCE OF ALL UNDER -GROUND
<br />UTILITIES IN WORK AREA PR TO CONSTRUCTION WITH A PRIVATE UTILITY
<br />LOCATOR.
<br />6. STANTEC ARCHITECTURE INC.. UNLESS OTHERWISE DETERMINED, SHALL APPLY
<br />AND PAY FOR ALL PERMITS REQUIRED FINK THE COMPLETION OF THIS
<br />PROJECT. CONTRACTOR TO SUPPLY CERTIFICATE O INSURANCE, CITY
<br />BUSINESS LICENSE, EVIDENCE OF CONTRACTORS UCENSE AND ANY OTHER
<br />ID'ORMATION WHICH THE PERMITTING AGENCY REWIRES FROM
<br />CONTRACTORS.
<br />7. GENERAL CONTRACTOR SHALL L NOTIFY THE ENGINEER PROMPTLY IF SITE
<br />CONDITIONS OR DIMENSIONS DISAGREE WITH INFORMATION SHOO ON THESE
<br />DRAWINGS. WORK IS NOT TO PROCEED LWM SUCH DIFFERENCES ARE
<br />RESOLVED.
<br />8, GENERAL CONTRACTOR SHALL PROVIDE A DETAKZD METHOD OF PROCEDURE
<br />M.O.P.) TO AT&T FOR APPROVAL PRIOR TO START OF CONSTRUCTION. MOP
<br />INCLUDE BUILDING VENTILATION SAFETY PROCEDURES.
<br />9. GENERAL CONTRACTOR SHALL SUPPLY AT&T WITH A DETAILED WORK
<br />SCHEDULE MID UPDATE PROGRESS AND/OR CHANGES ON A WEEKLY BASIS.
<br />10. APPROVED PAV SHALL PROVIDE THREE SETS O SUBMITTALS ON ALL
<br />EQUIPMENT TO THE ENGINEER PRIOR TO START OF CONSTRUCTION.
<br />11. ALL ELECTRICAL WORK TO BE DONE IN COMPLIANCE WITH CHAPTER 5,
<br />ARTICLES 500-50 AND 514 OF TNR' NATIONALELECTRIC COIF. SEAT ALL
<br />CONDUITS AS REWIRED UNDER THE CODE.
<br />12. APPROVED PAV SHALL SUPPLY FIVE COMPLETE SETS OF OPERATION,
<br />MAINTENANCE AND TEST DATA TO GENERAL CONTRACTOR. OPERATIONAL,
<br />MAINTENANCE AND TEST DATA SHALL INCLUDE ALL THE ITEMS LISTED ON
<br />SHEET F7 - PROJECT CLOSE-OUT DOCUMENTS AND CHECKLISTS. ALL
<br />DOCUMENTS TO BE IN ACCORDANCE WITH CURRENT AT&T EMS 200 SERIES
<br />PRACMES MW CHECKLISTS FOR REGULATORY BINDERS AND ON-SITE
<br />BINDERS.
<br />13. NEW TANKS AND PIPING SHALL BE TESTED IN ACCORDANCE WITH
<br />APPLICABLE REGULATIONS AND SPECIFICATIONS.
<br />14. THE GENERAL CONTRACTOR SHALL COMPLY WITH ALL DUST CONTROL
<br />REQUIREMENTS AS SET FORTH BY THE FACILITY SUPERVISOR OR HIS
<br />DESIGNATED REPRESENTAINE WHEN DRILLING, CORING. OR OTHERWISE
<br />MAKING HOLES OR PENETRATIONS INSIDE THE FACILITY BUILDING,
<br />INCLUDING SCREW HOLES FOR CONDUIT SUPPORTS. ETC. AS A MINIMUM
<br />EFFORT. THE CONTRACTOR SMALL CONTAIN AND COLLECT ALL DUST BY
<br />MEANS OF PLASTY SHEET ISOLATION OF THE WORK AREA AND VACUUMING
<br />THE DUST AS IT OCCURS.
<br />15. NO WORK SHALL BE PERFORMED OVER TELLPHDME SWITCH EQUIPMENT
<br />WITHOUT A MOP (METHOD OF PROCEDURE).
<br />16. AT&T ENDS SHALL PERFORM 6 MONTH COMPLIANCE TESTING. ANY FAILURES
<br />ARE THE RESPONSIBILITY OF THE INSTALLATION CONTRACTOR.
<br />17. PROVIDE MONITORING FOR EACH DAY TRIC THAT HAS A CAPACITY OF 100
<br />GALLONS OR MORE. REFER TO THE TANK /LEAK DETECTION
<br />SYSTEM ALARM SUMMARY FOR MONITORING REQUIREMENTS. ASSURE ALL
<br />SENSORS MEET CALIFORNIA STATE WATER RESOURCES CONTROL BOARD'S
<br />0RCB) MOST RECENT REOOREMENTS FOR EACH APPLICATION AS
<br />UNED IN SWRCB LETTER L0111
<br />18, PRIOR TO DISCONNECTING THE VEEDER ROOT ILS -350 MONITORING SYSTEM
<br />FOR ANY REASON, CONTRACTORS MUST NOTIFY THE CAM (CALIFORNIA
<br />ALARMS MANAGER) MO RECEIVE WRITTEN CONFIRMATION 48 HOURS IN
<br />ADVANCE OF ACTIVITY. CONTRACTORS MUST CONTACT THE CAM BY CALLING
<br />1-800-KNOW-EHS. THE DISCONNECT/MODIFCATON MUST BE DONE BY A
<br />VEEDER ROOT CERTIFIED LEVEL 4 TEC
<br />FINICIAN.
<br />19. CONTRACTOR SHALL CONTACT THE CALIFORNIA PERMIT MANAGER (CPM) AT
<br />1 -800 -KNOW -EIS SEVEN DAYS PRIOR TO INSTATING, RELOCATING OR
<br />REMOVING AND PORTION OR COMPONENTS ON THE MONITORING SYSTEM IN
<br />ANY CALIFORNIA UST FACILITY.
<br />29. TAUT &AWWAMEWAL SERMICE (TIES) MILL PIERFORm ALL COMPLIANCE TESTING
<br />FOR DSC PST SYSTEM PROJECTS WHRCH NCLIAffiSALLNOTPICATIONS.
<br />DOCUMMTAYMN, CERTIFICATIONS AND REPORTINGAS REQUYIEDRY THELOCAL
<br />AGENCY. TIE PAV M TO EXCLUDE ANY/ALL COSTS FOR COIVPUANCE TESTING AWN
<br />THEIR BIDS. THE GCAPAV WSl COAIV IN WWII THE LOCAL AGENCY WHAT TESTING ✓8
<br />AND INFORM TES. TES WILL PRDVME THE GCA PROPOSAL FOR SITE SPECIRC
<br />COA6PLJANCE TESTING, CONTRACT WITH 714E GC AND BILL THE GC FOR SERVICES.
<br />THE GC AND PAVMW.L COORDIATEWITH TES FORS OF THE TESTS.
<br />21. CONTRACTOR SHALL VERIFY EXACT TANK DIMENSIONS AND SIZE TANK SLAB
<br />PER MANUFACTURER'S WARRANTY AND STRUCTURAL DRAWINGS.
<br />22. IF ANY OF THE REQUIRE) COMPLIANCE TESTING HAS TO BE RESCHEOULED
<br />DDE TO A FARM TEST OR INCOMPLETE WADE¢ THE TANK CONTRACTOR
<br />WILL BE SOLELY MABLE FOR ANY AODITMNAL AND TESTING
<br />COSTS. ALL POTROLEUM STORAGE TANK SYSTEM WORK RELATED 70
<br />compLmmeE TESTING MUST 8E 400% COMPLETS, FUNCTIONAL AND
<br />READY FOR TESTING AND CERTIRCAT/OM (ML - ALL WIRING
<br />CONNECTIONS MADS, MNIT PROGRAMMED AND END-704DW
<br />COMNEC7WMVENFICA71ONS MADE LINES TORE GAIGC CHECKED,
<br />ISOLATED AND CAPPED/ BULKHEAD FITTINOS SECURE, CONTAINMENT
<br />80078 IN PLACE -ETC).
<br />Ft COVER SHEET AND NOTES
<br />F2 PIPING MODPICATION PLAN & NOTES
<br />F3 FUEL PIPING DETAILS
<br />F4 PROJECT CLOSE-OUT DOCUMENTS B CHECKLISTS
<br />ABBREVIATIONS:
<br />(E) EXISTING
<br />(N) NEW
<br />AM AUTHORITY HAVING JURISDICTION
<br />M ALLIANCE ARCHITECT
<br />AST ABOVEGROUND STORAGE TANK
<br />CMM CAUFORNM ALARM MANAGER
<br />CAPSEM CALIFORNIA PETROLEUM STORAGE TANK MANAGER
<br />CEC CALIFORNIA ENVIRONMENTAL CONSULTANT
<br />CPM CALIFORNIA PERMIT MANAGER
<br />CTM CALIFORNIA TESTING MANAGER
<br />DA DESIGN ARCHITECT
<br />WPM DESIGN AND CONSTRUCTION PROJECT MANAGER
<br />EAMC EMERGENCY ALARM MANAGEMENT CENTER
<br />EH&S ENVIRONMENT, HEALTH AND SAFETY
<br />EHSGC ENVIRONMENT, HEALTH. & SAFETY CONTROL CENTER
<br />ESM ENVIRONMENTAL SITE MANAGER
<br />ELD ENHANCED LEAK DETECTION
<br />FOR FUEL OL RETURN
<br />FOS FUEL OIL SUPPLY
<br />FOV FUEL OL VENT
<br />FRP FIBERGLASS REINFORCED PLASTIC
<br />GNFO GLOBAL. NETWORK FIELD OPERATOR
<br />LA LOCAL AUTHORITY
<br />NEC NATIONAL ELECTRIC CODE
<br />NFTS NATIONAL FUEL TANK SUPPORT
<br />NOC NETWORK OPERATIONS CENTER
<br />PAV PETROLEUM APPROVED VENDOR
<br />PST PETROLEUM STORAGE TANK
<br />PSTC PETROLEUM STORAGE TANK CONTRACTOR
<br />RA REVIEW AGENT
<br />U.G. UNDERGROUND
<br />USA UNDERGROUND SERVICE ALERT
<br />USI UNDERGROUND STORAGE TANK
<br />S" OBIM
<br />ENGINEERS, INC.
<br />�5 soin Ute sh®e:
<br />Sen /�, CA 95112-2218
<br />996 14th Street. Site 200 -
<br />WkN ' G 94612-2'25
<br />99 6 Poem Street
<br />y Monterey, CA 93M-1410(408) 282-1500
<br />PAY: (406) 8Y/-2.
<br />wwnsetmohrkn.rom
<br />REVISIONS AUTHORIZATIONS
<br />NT. 621E DATE BY
<br />ISSUE MR CUDIT ROVER (8D* 10/1/10 CS
<br />RESPONSE TO CLEW REVIEW (BOB) 11/1/10 CS
<br />FIRE DEPART" SUBMITTAL 3/15/11 CS
<br />C UPA SMMIITAL 4/07/11 CS
<br />PROPRIETARY AT&T INFORMATION
<br />NOT FOR ODI ML USE DA DOMMME OUTS O AT&T. TIS WOMAKDON INY
<br />ONLY E USED BY AUTHMZED PEBSOMMEL O THE LOCAL MOMENT AGM
<br />W COWWIDN WITH APRCAT01 FOR PERMITS AM NJ HM706 MR BUILDINGS
<br />AtB/ OR ZONES OWIGM
<br />DWINOS P. . a, FOR
<br />4' CORPORATE
<br />REALESTATE
<br />ABOVEGROUND
<br />FUEL PIPING MODIFICATIONS
<br />FOR STANDBY GENERATOR SYSTEM
<br />345 N. SAN JOAQUIN STREET
<br />STOCKTON,CA
<br />SKTNCA01 UE042
<br />SHEET TOLE:
<br />COVER SIFT
<br />AND NOTES
<br />PROJECT i - I CONSULTANT PROM $ 2007680049
<br />DATE 09/30/10 SCALE: AS NGIED
<br />- DRAWN BY: D6 DECKED BY: CBS
<br />AT&T 7mT: 1 OF: 4 SHEETS SHEET NO.
<br />BM Td 707.765.1660 AT&T NO-
<br />�j1
<br />Oft „37 U.S-IFGc 707.765.9008 - 1
<br />P9tdiR- CA A94954', -'-L
<br />94954 mvstwft 9m ROD SATRE 1
<br />
|