Laserfiche WebLink
SWRCB, January 2002 Page 5 of 5 <br />8. FILL RISER CONTAINMENT SUMP TESTING <br />Facility is Not Equipped With Fill Riser Containment Sumps ❑ <br />Fill Riser Containment Sumps are Present, but were Not Tested ❑ <br />Test Method Developed by ❑ Sump Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Specify) <br />Test Method Used ❑ Pressure ❑ Vacuum N Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used: Incon TS -STS Equipment solution: .0006 <br />Fill Sump # Middle Fill Sump # Fill Sump # Fill Sump # <br />UE042U001 �UE042UO01 <br />Sump Diameter: <br />38" <br />38" <br />Sump Depth: <br />41" <br />40.5" <br />Height from Tank Top to Top of <br />Highest Piping Penetration: <br />N/A <br />10" <br />Height from Tank Top to Lowest <br />Electrical Penetration: <br />14" <br />8" <br />Condition of sump prior to testing: <br />Good <br />Good <br />Portion of Sump Tested: <br />2" Above Collar <br />Sump Material: <br />Fiberglass <br />Fiberglass <br />Wait time between applying <br />pressure/vacuum/water and starting <br />test: <br />15 Min <br />Test Start Time: <br />10:20 AM 10:36 AM <br />Initial Reading Ri): <br />2.9936 2.9938 <br />Test End Time: <br />10:35 AM 10:51 AM <br />Final Reading (Rf): <br />2.9937 2.9935 <br />Test Duration: <br />15 Min 15 Min <br />Change in Reading Rf-Ri : <br />.0001 .0003 <br />Pass/Fail Threshold or Criteria: <br />.002 <br />.002 <br />Test Result: <br />N Pass ❑ Fail <br />❑ Pass N Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />Is there a sensor in the sump? <br />N Yes ❑ No <br />N Yes ❑ No <br />❑ Yes ❑ No <br />❑ Yes ❑ No <br />Does the sensor alarm when either <br />roduct or water is detected? <br />❑ Yes N No ❑ NA <br />❑ Yes N No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />Was sensor removed for testing? <br />N Yes ❑ No ❑ NA <br />❑ Yes N No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />Was sensor properly replaced and <br />verified functional after testing? <br />❑ Yes N No ❑ NA <br />11 <br />❑ Yes N No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />1 <br />❑ Yes ❑ No ❑ NA <br />Comments include any information on repairs made prior to testing,and recommended follow-up for failed tests <br />The Middle Sump sensor were reinstalled to the lowest point, but not tested. <br />The Fill Sump is a visual failure due to the Vent Secondary cracked test boot. Did not put any test water into the fill sump. <br />