Laserfiche WebLink
TA I T SEP 0 9 2016 <br /> .1—.TO 1..c„.iiir+ce M. 2131 S Du, ,�� C>n.,:. An.w CA 92806 <br /> SUMMARY TEST REPORT FOR USE WITH LEIGHTON O'BRIEN PM2 LINE TESTER <br /> CLIENT: AT&T UE042 DATE: 811712016 <br /> LOCATION: 345 North San Joaquin St. Stockton California 95202 <br /> Street City State <br /> REASON FOR TEST: Annual Request.Noncompliance test <br /> SPECIAL INSTRUCTIONS: Test conducted for above ground pressurized line. <br /> I declare under penalty of perjury that 1 am a licensed tank tester in the State of <br /> California and that the information contained in this report is true and correct to the <br /> best of my knowledge. <br /> TECHNICIAN: Pat Banbury -i'' N 90-1413 <br /> Name Signature License Number <br /> MAKE AND TYPE OF PUMP OR DISPENSERS Transfer Pump <br /> COVER OVER LINES Above Ground APPROX. BURIAL DEPTH NA <br /> Product Name Line Test Wet Test Start Test End Test Cert No. Test Results <br /> or Dry Time Time Pressure <br /> Diesel UE0420001/ WET 12:45 PM 13:03 PM 51.37 PSI 50264 Pass <br /> UE042AO05 0.120 al/hr. <br /> COMMENTS: Test conducted from UE0420001 above ground transfer pump to UE042AOOS roof top belly tank. <br /> Note:These results need to be submitted with the final Leighton O'Brien UPSS Test Report. <br />