Laserfiche WebLink
NDE'S VPLT COMPUTERIZED TANK TESTING SYSTEM Patent Pending <br />PRECISION UNDERGROUND TANK TESTING RESULTS AND CERTIFICATION <br />PAGE 1, SHORT REPORT FORM - Copyright 1985 <br />NDE TECHNOLOGY, INC. PROPRIETARY <br />TEST DATE: 06/02/89 <br />1. Owner of storage tanks PAC BELL <br />Company Representative Steve Wat <br />Title <br />2. Mailing address of owner 3707 Kings Way #A-4 <br />Sacramento, CA 95851 <br />3. <br />Phone of owner <br />(916) 972-2417 <br />4. <br />STATION NUMBER <br />U8058 <br />Location and address of <br />10 E. 12th St. <br />the tanks <br />Tracy, CA 95376 <br />Phone number <br />N/A <br />Regulatory Agency <br />County of San Joaquin <br />5. <br />TANK DESIGNATION OR ID # <br />Diesel <br />6. <br />Date each tank was tested <br />06/02/89 <br />7. <br />The name of the test method <br />VPLT COMPUTERIZED TANK TESTING SYSTEM <br />8. <br />Business name of tank <br />testing company <br />WESTERN AMERICA TANK TESTING, INC. <br />9. <br />Mailing address of tank <br />3131 FAIRHAVEN DRIVE <br />testing company <br />BAKERSFIELD, CA 93308 <br />10. <br />Person conducting test <br />Ken Brown (TECHNICIAN) <br />and completing report <br />11. <br />Station Operator or <br />N/A <br />manager <br />12. <br />Phone number <br />N/A <br />13. <br />Owner name and <br />PAC BELL <br />title <br />14. <br />Capacity of the tank <br />1,500 gallons <br />15. <br />Present or past contents <br />Diesel <br />16. <br />Tank construction material <br />Unknown <br />17. <br />Testing fluid <br />Diesel <br />THE UNDERGROUND STORAGE TANK SYSTEM CERTIFIED TIGHT AT PRODUCT <br />HEIGHT EQUAL TO THE GRADE LEVEL. Yes. <br />Allowable leak resolution of instrumentation or allowable change <br />per California Administrative Code Title 23 Waters, Chapter 3 <br />Water Resources Control Board Subchapter 16 Underground Storage <br />Regulations, Part 2643 (b), Page 4.14; 0.05 gallons per hour. <br />MEASURED HOURLY CHANGE: LOSS (+) OR GAIN (-) GALLONS OR <br />NUMERICAL LEAK RATE IS: -0.001 Gal/Hr. <br />This measurement is within the legal limits as defined in (b). <br />NDE TECHNOLOGY, INC. PROPRIETARY <br />WATT INC. 3131 FAIRHAVEN DRIVE, BAKERSFIELD, CA 93308 (805) 322-9827 <br />