Laserfiche WebLink
SUMMARY OF UNDERGROUND STORAGE TANK SYSTEM TESTING <br />NDE ENVIRONMENTAL CORPORATION <br />20000 Mariner Avenue, Suite 500 <br />Torrance, California 90503 <br />(310) 542-4342 <br />Test Date: 30 Oct 1992 worK Uraerff: V0v»o <br />PACIFIC BELL PACIFIC BELL <br />6801 ALMAD_EN RD 10 E. 12TH ST. <br />SAN JOSE , CA 95120 TRACY , CA 95376 <br />Attn: LYLE STUCK <br />The following tests were conducted at the site described above in accordance <br />with all applicable portions of federal, NFPA, and local regulations. <br />TANK SYSTEM INFORMATION <br />Tank <br />No. <br />Tank <br />Capacity <br />Tank <br />Diameter <br />Product <br />Product <br />Level <br />Tank <br />Material <br />Vapor <br />Recovery <br />Type <br />#809 <br />1,700 <br />59 <br />DIESEL <br />45.00 <br />STEEL <br />N/A <br />NO <br />TESTING RESULTS <br />Tank <br />No. <br />VPLT <br />Volume <br />Change <br />(gph) <br />Wetted <br />Portion <br />of Tank <br />Pass/fail <br />Ullage <br />Portion <br />of Tank <br />Pass/Fail <br />Product <br />Lines <br />Pass/Fail <br />Vent & <br />Vapor <br />Lines <br />Pass/Fail <br />Leak <br />Detector <br />Present? <br />Yes/no <br />Leak <br />Detector <br />Results <br />Pass/Fail' <br />#809 <br />-0.007 <br />PASS <br />PASS <br />PASS <br />PASS <br />NO <br />NDE appreciates the opportunity to serve you, and looks forward to working with <br />you in the future. Please call any time, day or night, when you need us. <br />NDE Customer Service Representative Testing conducted by <br />F. MILLER J. CONGER <br />