Laserfiche WebLink
8. F RISER CONTAINMENT SUMP TE§WG <br /> Test Method Developed By: ❑ Sump Manufacturer ®Industry Standard ❑Professional Engineer <br /> ❑ Other(Specify) <br /> Test Method Uses: ❑Pressure ❑Vacuum ®Hydrostatic <br /> ❑Other(Specify) <br /> Measuring Equipment Used for Testing: Tempsonic <br /> Fill Sump# Fill Sump# Fill Sump# <br /> Sump Diameter: 30" <br /> Sump Depth: 54 ''/2" 7 <br /> Height from Tank Top to N/A <br /> Highest Piping Penetration: <br /> Height from Tank Top to 21# <br /> Lowest Electrical Penetration: <br /> Condition of sump prior to CLEAN <br /> testing: <br /> Portion of Sump Tested ABOVE PENETRATION <br /> Sump Material: FIBERGLASS <br /> Wait time between applying 15 MIN <br /> pressure/vacuum/water and <br /> starting test: <br /> Test Start Time: 8:10 8:30 <br /> Initial Reading(RI): 7.920 7.920 <br /> Test End Time: 8:25 8:45 <br /> Final Reading(RF): 7.920 7.920 <br /> Test Duration: 15 MIN 15 MIN <br /> Chane in Reading(RF-Ri): 0 0 <br /> Pass/Fail Threshold: .002 <br /> Test Result: PAS <br /> Is there a sensor in the sump? YES <br /> Does the sensor alarm when YES <br /> either product or water is <br /> detected? <br /> Was sensor removed for YES <br /> testing? <br /> Was sensor properly replaced YES <br /> after testing? <br /> Comments—(include information on repairs made to facilitate a passing test and indicate whether a <br /> permit was obtained for the repairs) <br /> R.C.U.S.T.COM <br />