4. ® SPILL/OVERFILL CONTAINMENT BOX <br />Facility is Not Equipped With Spill/Overfill IMtainment Boxes <br />Spill/Overfill Containment Boxes are Present, but were Not Tested <br />Test Method Developed By: Spill Bucket Manufacturer ® Industry Standard Professional Engineer <br />Other (Specify) <br />Test Method Used: Pressure Vacuum ® Hydrostatic <br />Other (Specify) <br />Test Equipment Used: MARKER / VISUAL Equipment Resolution: N/A <br />f' Spill Box # 1 Spill Box Spill Box # Spill Box # <br />Y DIESEL FILL <br />Bucket Diameter: 12" <br />Bucket Depth: 11" <br />Wait time between applying <br />pressure/vacuum/water and 5 MINUTES <br />starting test: <br />Test Start Time: 11:30 <br />Initial Reading (Ri): 6" <br />Test End Time: 12:30 <br />Final Reading (RF): 6" <br />Test Duration: 1 HOUR <br />Change in Reading (RF-Ri): 0 <br />Pass/Fail Threshold or 0 <br />Criteria: <br />Test Result: Pass Fail ❑ Pass Fail Pass Fail Pass Fail <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />