Laserfiche WebLink
&A F1yVI�tG?N11 EN�'AL i <br /> 5643 BROOKS CT BAKERSFIELD,CA.93308 <br /> OFFICE(661)392-8687 & FAX (661)392-0621 <br /> SRT 1000 MMERIULL-MM ALERT 1050x UI,LAGE SySTE_ <br /> Precision Underground Storage Tank System Leak Test <br /> TEST RESULTS <br /> Test Date: 09/09/99 <br /> BILLING:CONFIDENCE UST SER. SITE:BEACON <br /> 417 MONTCLAIR ST. 1001 E. YOSEMITE <br /> BAKERSFIELD, CA.93309 MANTECA, CA <br /> 7-7 PRODUCT VOL %FULL WETTED NON-WETTED PRODUCT LEAK WATER IN <br /> ( ) PORTION PORTION LINE-- DETECTOR TAM <br /> UNLEADED 12000 72%- -0.004 PASS NO TEST 0'° <br /> PREMIUM 8000 76# +0.024 PASS NO TEST 010 <br /> DIESEL 4000 49% NO TEST NO TEST NO TEST 0°A <br /> WA RNALME <br /> Measurements showed that water in the backfill area at the time <br /> of testing was below tank bottom, and therefore not a factor in test <br /> determination. A monitoring well or a well point was driven in the <br /> backfill area to determine that there is no water in the backfill at <br /> tank bottom. <br /> A precision test was performed on tanks at the above location using the <br /> Alert 1000 underfill system and the Alert 1050x ullage system. I have <br /> reviewed the data produced in conjunction with this test for purpose of <br /> verifying the results and certifying the tank systems. The testing was <br /> performed in acorrdance with Alert protocol, and therefore satisfies <br /> all requirements for such testing as set forth by NFPA 329-92 <br /> and USEPA 40 CFR part 280. <br /> The results of testing are shown on the following page, and indicate <br /> whether the wetted and non-wetted portion passed or failed. Included <br /> with the report are reproduction of data compiled during the test which <br /> formed the basis for these conclusion. This information is stored in a <br /> permanent file if future verification of test results is needed. <br /> AL\NC 040 <br /> Tes Certified By: <br /> a <br /> es J. ich <br /> tate cert99-1072 <br />