PLC-50 with the 98 LD-2000 PLC <br /> Table 5. Data Sheet Summarizing the Test Results and the Leak Rates Used in the Evaluation <br /> for the Monthly/Annual Tests (0.1 gal/h) <br /> Test No. Date Induced Time between End Time Data Time Data Measured Was <br /> (Based on Test Leak Rate of Circulation and Collection Collection Test Threshold <br /> Temperature Began Start of Data Began Ended Result Exceeded? <br /> Condition) Collection for Test <br /> D-M-Y al/h) (h-min local milita local military) leak or tight) es or no <br /> Rigid -43 8-Jan-98 0.1 0-0 1911 0239 Leak Yes <br /> Rigid -44 29-Jan-98 0 0-0 1101 1435 Tight No <br /> Rigid -45 7-Jan-98 0.1 0-0 1250 1957 Leak Yes <br /> Rigid -46 28-Jan-98 0.1 0-0 0850 1506 Leak Yes <br /> Rigid-47 9-Jan-98 0.1 0-0 0940 1542 Leak Yes <br /> Rigid-48 6-Jan-97 0.1 0-0 1040 1848 Leak Yes <br /> Ri id-49 10-Jan-98 0.1 0-0 1135 1749 Leak Yes <br /> Rigid-50 31-Jan-98 0 0-0 1422 1815 Tight No <br /> Rigid -51 30-Jan-98 0 0-0 1157 1559 Ti ht No <br /> Rigid -52 3-Jan-97 0.1 0-0 1255 2053 Leak Yes <br /> Rigid -53 17-Dec-97 0 0-0 1441 1916 Tight No <br /> Rigid -54 1-Dec-97 0 0-3 2021 0048 Tight No <br /> Rigid -55 7-Dec-97 0.1 0-1 0721 1556 Leak Yes <br /> Rigid -56 1-Dec-97 0.1 0-1 1001 1756 Leak Yes <br /> V-1 1-Feb-98 0 0-0 1622 1945 Tight No <br /> V-2 2-Feb-98 0.1 0-0 0925 2056 Leak Yes <br /> V-3 6-Feb-98 0.1 0-0 1015 1620 Leak Yes <br /> Flex-1 2-Mar-98 0.1 0-0 1142 1617 Leak Yes <br /> Flex-2 3-Mar-98 0 0-0 1805 0255 Tight No <br /> Flex-3 23-Feb-98 0.1 0-0 0728 1226 Leak Yes <br /> Flex-4 23-Feb-98 0 0-0 1416 2238 Tight No <br /> Flex-5 19-Feb-98 0 0-0 1827 2114 Tight No <br /> Flex-6 20-Feb-98 0.1 0-0 1212 1840 Leak Yes <br /> Page 15 <br />