Laserfiche WebLink
PLC-5000 with the 98 LD-2000,PLC <br /> Table 7. Data Sheet Summarizing the Test Results of the Trapped Vapor Tests <br /> Summary of Temperature Conditions <br /> Test No. Date Test Nominal Time Time Duration of Time of T(TB) T(1) T(2) T(3) T(G) T(TB)-T(G) Temperature <br /> (Based on Began Product Circulation Circulation Circulation Temperature Test <br /> Temperature Temperature Started Ended Measurements Matrix <br /> Condition) Before Category <br /> Circulation <br /> Was Started <br /> (D-M-Y) (deg F) (local military) (deg F) (h-min) (local military) (deg F) (deg F) (deg F) (deg F) (deg F) (deg F) (Table 5. <br /> V-1 1-Feb-98 51.80 1522 1622 1-0 1522 51.80 40.40 42.00 41.10 41.22 10.58 +5 to+15 <br /> V-2 2-Feb-98 62.40 0825 0925 1-0 0825 62.40 41.60 42.90 42.20 42.29 20.11 +15 to+25 <br /> V-3 6-Feb-98 58.00 0915 1015 1-0 0915 58.00 50.50 51.20 50.30 50.52 7.48 +5 to+15 <br /> Summary of Leak Rates <br /> Test No. Date Test Pipeline Induced Leak Time between End of Time Data Time Data Measured Was Threshold <br /> Began Pressure Rate Circulation and Start of Collection Began Collection Ended Test Exceeded? <br /> Data Collection for Test I Result <br /> (D-M-Y) (psi) (gal/h) (h-min) (local military) (local military) (leak or tight) (yes or no) <br /> V-1 1-Feb-98 nominal 30 0 0 1522 1945 Tight No <br /> V-1 2-Feb-98 nominal 30 0.1 0 0825 2056 Leak Yes <br /> V-1 6-Feb-98 nominal 30 0.1 0 0915 1620 Leak Yes <br /> Page 17 <br />