Laserfiche WebLink
D <br /> SWRCB,January 2002 Page of <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: ❑Tank Manufacturer Andustry Standard ❑Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑ Pressure /Vacuum ❑ Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: VACCUM GAUGE Equipment Resolution: "HG <br /> 0 PROEM, <br /> lfflatz�� Tank# 87 Tank#91/DSL Tank# Tank# <br /> Is Tank Exempt From Testing?' ❑Yes filo ❑Yes Xio C Yes ❑No ❑Yes ❑No <br /> Tank Capacity: 12K 12K <br /> Tank Material. FIBERGLASS FIBERGLASS <br /> Tank Manufacturer: UNKNOWN UNKNOWN <br /> Product Stored: GAS GAS/DIESEL <br /> Wait time between applying <br /> pressure/vacuum/water and 5 MIN 5 MIN <br /> starting test: <br /> Test Start Time: 1039 1039 <br /> Initial Reading(Rj): 10" 10" <br /> Test End Time: 1139 1139 <br /> Final Reading(RF): 9" 9" <br /> Test Duration: IHR IHR <br /> Change in Reading(RF-Ri): 1" 1" <br /> Pass/Fail Threshold or Criteria: 2" 2" <br /> Test Result: O-Pass ❑Fail ('Pass ❑Fail ❑ Pass ❑Fail ❑ Pass ❑Fail <br /> Was sensor removed for testing? Q'Yes ❑No ❑NA "Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes []No ❑NA <br /> Was sensor properly replaced and <br /> verified functional after testing? es ❑No ❑NA I�Yes ❑No ❑NA ❑Y-s []No ❑NA ❑Yes ❑No ❑NA <br /> Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> 91/DSL ISA SPLIT TANK <br /> 1 Secondary containment systems where the continuous monitoring automatically monitors oth the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23, Section 2637(a)(6)} <br />