Laserfiche WebLink
SWRCB,January 2002 Page of <br /> 7. UNDER-DISPENSER CONTAINMENT UDC TESTING <br /> Test Method Developed By: ❑UDC Manufacturer Andustry Standard ❑Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑Pressure ❑Vacuum 'Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used: INCON TS STS Equipment Resolution: .000 1 INCHES <br /> W777= sm, <br /> UDC# 1-2 UDC#3-4 UDC#5-6 UDC#7-8 <br /> UDC Manufacturer: BRAVO BRAVO BRAVO BRAVO <br /> UDC Material: STEEL STEEL STEEL STEEL <br /> UDC Depth: 10 10 10 10 <br /> Height from UDC Bottom to Top 0 0 0 0 <br /> of Highest Piping Penetration: <br /> Height from UDC Bottom to 0 0 0 0 <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to GOOD GOOD GOOD GOOD <br /> testing: <br /> Portion of UDC Tested 3" 3" 3" 3" <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both ❑Yes ❑No C3 NA 11 Yes ❑No ?NA ❑Yes ❑No C�lA ❑Yes []No A <br /> product and water)? <br /> Turbine shutdown response time <br /> Is system programmed for fail- 11 Yes ❑No IKNA ❑Yes ❑No XA ❑Yes ❑No 2�1A ❑Yes ❑No ?<A <br /> safe shutdown?* <br /> Was fail-safe verified to be ❑Yes ❑No [AA ❑Yes ❑No [IA ❑Yes ❑No ? A ❑Yes ❑No A <br /> operational?* <br /> Wait time between applying <br /> pressure/vacuum/water and <br /> starting test <br /> Test Start Time: 11:02 11:02 12:03 12:03 <br /> Initial Reading(Rj): 0.3388 0.1434 0.7301 0.2366 <br /> Test End Time: 11:17 11:17 12:18 12:18 <br /> Final Reading(RF): 0.3382 0.1433 0.7287 0.2367 <br /> Test Duration: 15 MIN 15 MIN 15 min 15 min <br /> Change in Reading(RF-RI): 0.0006 0.0001 0.0014 0.0001 <br /> Pass/Fail Threshold or Criteria: .002 .002 .002 .002 <br /> Test Result: 2Pass ❑Fail Er Pass ❑Fail [R-Pass ❑Fail IT-Pass ❑Fail <br /> Was sensor removed for testing? 1-Yes ❑No ❑NA Z Yes ❑No ❑NA Aes ❑No ❑NA C'Yes ❑No ❑NA <br /> Was sensor properly replaced and <br /> verified functional after testing? A� es LEINo �NA [2'Yes 11 No ❑NA [ln_. 11 No ❑NA fifes ❑No ❑NA <br /> Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> ' If the entire depth of the UDC is not tested,specify how much was tested. If the answer to�Lny of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />