Laserfiche WebLink
The following is an itemized list of underground storage tank violations that have not <br />been addressed for 76 MINI MART as of June 07, 2016. <br />Open violations from January 29, 2016 inspection <br />Violation #207 - Designated operator did not inspect all required items and/or the inspection reports not <br />completed. <br />The designated operator failed to check and note the correct test dates for the secondary containment testing on all <br />2015 designated operator monthly inspection reports. According to the received secondary containment testing <br />results, the secondary containment testing was conducted on 3-2-2015; the designated operator reports list it as <br />3-18-2015. During the monthly inspection, the designated operator shall check that all required testing and <br />maintenance for the UST system have been completed and document the dates they were done. Ensure that <br />designated operators performing monthly inspections at this facility are including all of the required information on the <br />reports. <br />Violation #209 - Designated operator employee training not performed or log not kept. <br />1) The designated operator employee training log doesn't contain all the required information, the employee hire <br />dates were not provided for Mr. Mangir Singh and for Mr. Hartaj Singh. The designated operator shall train facility <br />employees for which he or she is responsible in the proper operation and maintenance of the UST system once <br />every 12 months. The training shall include, but is not limited to: <br />1. Operation of the UST system in a manner consistent with the facility's best management practices <br />2. Employee's role with regard to monitoring equipment as specified in the facility's monitoring plan <br />3. Employee's role with regard to spills and overfills as specified in the facility's response plan <br />4. Name of the contact person(s) for emergencies and monitoring equipment alarms <br />Ensure that all employees have been trained by the designated operator, maintain the list on site, and submit a copy <br />of the complete training records to the EHD. <br />2) According the the February 18, 2015 routine underground storage tank inspection, no employee training was <br />conducted for this facility. The employee training log was observed at the time of the most current inspection. <br />Open violations from February 18, 2015 inspection <br />Violation #204 - Current monitoring plan approved by the EHD not found on site. <br />An approved copy of the monitoring plans were not available for inspection. A copy of these plans shall be <br />accessible on site at all times. Immediately locate and retain a copy on site. This is a minor violation. <br />Page 2 of 2 <br />