Laserfiche WebLink
SWRCB,January 2002 Page of <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: X Tank Manufacturer ❑Industry Standard ❑Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure X Vacuum ❑Hydrostatic <br /> 11 Other(Spec) <br /> Test Equipment Used: Gast Vacuum Pump/Vacuum Gauge in Hg. Equipment Resolution: - '/2"x-30"Hg. <br /> Tank# 1 Tank# Tank# Tank# <br /> Is Tank Exempt From Testing?' No <br /> Tank Capacity: 12K <br /> Tank Material: Fiberglass ? , <br /> Tank Manufacturer: Owens Corning UIL <br /> Product Stored: Jet A 3UL 2 7 '!Ml <br /> Wait time between applying 10 Minutes <br /> vacuum and starting test: ; t� <br /> Test Start Time: 8:50 t B`;"�� °``"-` fi <br /> Initial Reading(RI): -10"Hg. <br /> Test End Time: 9:50 <br /> Final Reading(RF): -10"Hg. <br /> Test Duration: 1 Hour <br /> Change in Reading(RF-RI): 0"Hg. <br /> Pass/Fail Threshold or Criteria: No loss in Hg. <br /> Test Result: Pass <br /> Was sensor removed for testing? No <br /> Was sensor properly replaced and N/A <br /> verified functional after testin ? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23,Section 2637(a)(6)) <br />