Laserfiche WebLink
Triangle Environmental, Inc. <br /> 2525 West Burbank Blvd.,Burbank,CA 91505-2302 <br /> (818)840-7020 (818)840-6929 <br /> UST TESTING SYSTEMS SUMMARYSHEET <br /> Precision Underground Storage Tank System Leak Test <br /> Client: <br /> Conoco Phillips Co. Facility # 2611194 <br /> 1500 North Priest Drive <br /> Tempe, AZ 85281 Test Date: 5/12/03 <br /> Kathy Strickland <br /> (602)728-7149 30224 <br /> Facility: 2611194 Work#: 20000603 <br /> Facility#2611194 County: SAN JOAQUIN <br /> 2375 TRACY BLVD Cross Street: SWC TRACY BLVD&GRANT LINE <br /> TRACY, CA 95376 <br /> Tank Test System Tank Line <br /> # Product Capacity Type Rate/Results Ullage Result Rate/Result L/D Result <br /> 1 Unleaded Regular 11763 System 4000 N/A N/A N/A PASS <br /> 2 Unleaded Premium 9816 System 4000 N/A N/A N/A PASS <br /> 3 Unleaded Plus 9816 System 4000 N/A N/A N/A FAIL <br /> Certified By: Technician: Tom Corcoran State Lic.#s: 02-1626 <br /> Mfgr's M TEI-067 <br /> VR-7539 <br /> Comments: <br /> Compliance L/D&monitor certification&IF.Product lines not required. Station has dispenser pan sensors. <br /> This precision tank testing system has been third party evaluated according to the guidelines of the EPA <br /> procedures for annual leak detection systems and found to exceed the criteria of detecting a leak of 0.10 <br /> gph with a Pd>95% and Pfa<5% as required by Local,State and Federal EPA UST Technical <br /> Standards Part 280 for precision testing systems. This SB-989 secondary containment testing system <br /> exceeds the criteria for detection as required by state and local agencies. <br />