Laserfiche WebLink
Triangle vir ental Inc <br /> SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Tosco Facility # 30224 <br /> Tank #: 3 Test Date: 8/ 6/01 <br /> Product: Unleaded Plus Work#: 12900611 <br /> EMENEENEEM <br /> Test Method: Test Method: R.J.FTA <br /> Capacity: 9816 Manufacturer: Vaporless <br /> Diameter(in): L/D Model: LD2000 <br /> Product Level(in): L/D Serial#: <br /> Liquid Volume(Gals): Line Drain Back(ml): 84 <br /> Liquid Percent(%): L/D Trip Time(sec): 2 <br /> Specific Gravity: Holding Pressure(psi): 27 <br /> Coef. of Expansion: Metering Pressure(psi): 21 <br /> Water On Tank(in): L/D Test Rate(gph): 1.1 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): New leak detector? No <br /> Head Pressure(psi): <br /> Test Start Time: <br /> Test End Time: Test Method: <br /> Test Rate(gph): <br /> Pump Brand: Red Jacket <br /> Test Res : N/A System Type: Pressure <br /> WIN Line Pressure(psi): <br /> Line Start Time: <br /> Test Method: ULLAGE Line End Time: <br /> U11ageVolume(gals.): i Line Start Level: <br /> Ullage Test Time: Line End Level: <br /> h <br /> Ullage Vacuum(psi): Line Test Rate(� ): <br /> Ullage Result: N/A Line Test Result: N/A <br /> retest on new LD <br /> 3 <br />