Laserfiche WebLink
Triangle Environmental Inc <br /> 2525 West Burbank Blvd.,Burbank,CA 91505-2302 <br /> (818)840-7020 (818)840-6929 <br /> UST TESTING SYSTEMS°S UMMAR Y SHEET <br /> Precision Underground Storage Tank System Leak Test <br /> Client: <br /> Tosco Marketing Co. TOSCO Facility # 30224 <br /> 1500 North Priest Drive <br /> Tempe, AZ 85281 Test Date: 8/ 6/01 <br /> Kathy StrickLand <br /> (602)728-7149 <br /> Facility: 2611194 Work#: 12900611 <br /> Tosco Facility# 30224 County: SAN JOAQUIN <br /> 2375 TRACY BLVD Cross Street: SWC TRACY BLVD&GRANT LINE <br /> TRACY, CA 95376 <br /> Tank Test System Tank Line <br /> # Product Capacity Type Rate/Results Ullage Result Rate/Result L/D Result <br /> 1 Unleaded Regular 11763 N/A N/A N/A PASS <br /> 3 Unleaded Plus 9816 N/A N/A N/A PASS <br /> Certified By: Technician: Tom Corcoran State Lic.#s: <br /> Mfgr's#: <br /> Comments: / o <br /> This precision tank testing system has been third party evaluated according to the guidelines of the EPA <br /> procedures for annual leak detection systems and found to exceed the criteria of detecting a leak of 0.10 <br /> gph with a Pd>95% and Pfa<5% as required by Local,State and Federal EPA UST Technical <br /> Standards Part 280 for precision testing systems. This SB-989 secondary containment testing system <br /> exceeds the criteria for detection as required by state and local agencies. <br />