Laserfiche WebLink
Triangle vi a , Inc. <br /> UST MONITOR CE TIFICATIONSU MARYSHEET <br /> Client: <br /> Conoco Phillips Co. <br /> 600 N Dairy Ashford Facility # 2611194 <br /> Houston, 2 X117079 4 <br /> est Date: 5/10/04 <br /> Facility. 6 9 <br /> Facility # 2611194 Work#: 20005420 <br /> 2375 TRACY BLVD County: SAN JOAQUIN <br /> Cross Street: SWC TRACY BLVD& <br /> TRACY, CA 95376 <br /> Monitor model: VEEDER-ROOT TLS-350 <br /> Serial#: 50333371605001 Certification Result: PASS <br /> Sensor Type: Quantity: Result: <br /> Tank Annular : 3 Pass Annular Type: 409 <br /> Waste Oil Annular : 1 Pass Audible Alarm? Yes <br /> Waste Oil Sump: 0 N/A Visual Alarm? Yes <br /> Vadose Wells : 0 N/A Fail Safe? Yes <br /> Line Pressure : 0 N/A Positive Shut-off. Yes <br /> Turbine Sump : 3 Pass Gauge Only Result: Pass <br /> Line Trench : 0 N/A ATG Monthly? No <br /> Fill Sump : 0 N/A ATG CSLD? No <br /> Comments: <br /> Replaced 89 Leak detector with LD2000. There was about 1 gallon of fuel in the 87 turbine <br /> sump due to leaking vent screw check valve. <br /> This certifies that the monitor and sensors,as listed above,are operational and calibrated per the <br /> manufacturer's specification. <br /> Inspected By: <br /> Ronnie Humphries �9/ <br />