Laserfiche WebLink
D. Results of Testing/Servicing <br />Software Version installed: 329.01 <br />Cninnlata the followina checklist: <br />® Yes <br />❑ No' <br />is the audible alarm operational? <br />® Yes <br />❑ No' <br />Is the visual alarm operational? <br />® Yes <br />❑ No` <br />Were all sensors visually inspected, functionally tested, and confirmed operational? <br />® Yes <br />❑ No` <br />Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not Interfere with their proper <br />operation? <br />❑ Yes <br />❑ No' <br />If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem) operational? <br />® N/A <br />❑ Yes <br />❑ No' <br />For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment monitoring system detects a leak, <br />® NIA <br />fails to operate, or is electrically disconnected? If yes: which sensors initiate positive shut -down? (Check all that apply) ❑ SumpfTranch <br />Sensors; ❑ Dispenser Containment Sensors. <br />Did you confirm positive shut -dawn due to leaks wd sensor failure/disconnection? ❑ Yes: ❑ No. <br />❑ Yes <br />❑ No' <br />For tank systems that utilize the monitoring system as the primary tank overfill warning device p.e., no mechanical overfill prevention valve is <br />® N/A <br />installed), is the overfill warning alarm visible and audible at the tank fill point(s) and operating property? if so, at what percent of tank capacity <br />does the alarm trigger? °! <br />❑ Yes <br />® No <br />Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the manufacturer name <br />and model for all replacement parts in Section E, below. <br />❑Yes' <br />® No <br />Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) <br />❑ Product; ❑ Water. If yes, describe causes in Section E, below. <br />tiYes <br />❑ No' <br />Was monitoring system set-up reviewed to ensure proper settings? Attach set up reports, if applicable <br />❑ Yes <br />® No' <br />Is all monitoring equipment operational per manufacturer's specifications? <br />` in Section E below, describe how and when these deficiencies were or will be corrected. <br />E. comments: VEEDER ROOT WAS NOT WORKIN PROPERLY. <br />SENSORS WOULD NOT SHUTDOWNi. .R,a REPAIRS <br />WE WERE UNABLE TO FINISH MONITOR <br />Monitoring System certification Page 2 of 4 2/21/07 <br />