Laserfiche WebLink
Triangle Environmental, Inc. <br /> T.E.I.SYSTEMS TANK, LINE.AND LEAK DETECTOR TEST REPORT <br /> Facility: QLTIKSTOP #00144 <br /> Tank : 1 Work#: 30919 <br /> Product: Unleaded Regular Test Date: 12/2 /98 <br /> Test Method: Fest Method: RJ.FTA <br /> I. <br /> Capacity: ! Manufacturer. Red Jacket <br /> Diameter(in): !/D Model: XLD I <br /> Product Level(in): I LID Serial 4: 10192-0717 <br /> Liquid Volume(Gals): Line Drain Back(ml): 45 <br /> Liquid Percent("/o): I L/D Trip Time(sec): 2 <br /> Specific Gravity: I Holding Pressure(psi): 14 <br /> Coat of Expansion: Metering Pressure(psi): 10 <br /> Water On Tank(in): i L/D Test Rate(gph): 0.8 <br /> Water In Tank(in): i L/D Result: PASS <br /> Product Tem (F): ; ;__..._.. . ..._ ....^_ _..... .._ <br /> Head Pressure(psi): <br /> Test Stats Time: <br /> Test Method: TEI LT-3 <br /> Test End Time: Pump Brand: Red Jacket <br /> Test Rate(gph). ( i System Type: Pressure <br /> Test Result: N/A i I <br /> I <br /> Line Pressure(psi): 50 <br /> i <br /> Line Start Time: 2:50 PM <br /> Test Method: ULLAGE Line End Time: 3:05 PM I <br /> I UllageVolume(gals.): i Linc Start Level: 220 <br /> Ullage Test Time: I Line End Level: 195 <br /> Ullage Vacuum(psi): I Line Test Rate(gph): -0.026 <br /> Ullage Result: N/.A. Line Test Result: PASS <br /> I ' <br /> PSD <br /> z i <br />