Laserfiche WebLink
Triangle Environmental, Inc. <br /> T.E.I. SYSTEMS TANK,LINE AND LEAK DETECTOR.TEST REPORT <br /> MMr�99p <br /> Facility: QUIKSTOP #00144 <br /> Tank#: 3 Work#: 30919 <br /> Product: Unleaded Plus Test Date: 12/2 /98 <br /> i <br /> Test Method- 1 Test Method: R.J.FTA <br /> Capacity: Manufacturer: Red Jacket <br /> Diameter(in): LID Model: FX <br /> Product bevel(in): ! L/D Serial#: 10598-9230 <br /> Liquid Volume(Gals). Line Drain Back(ml): 135 <br /> Liquid Percent(%): i L/D Trip Time(sec): 3 <br /> I Specific Gravity: I Holding Pressure(psi): 14 <br /> Coef.of Expansion: Metering Pressure(psi): 11 <br /> Water On Tank(in): I L/D'Test Rate(gph): 1.0 <br /> Water In Tank(in): LID Result: PASS <br /> Product Temp. (F): i <br /> i <br /> Head Pressure(psi): <br /> i Test Start Time: i Test Method: TEI LT-3 <br /> "Gest End Time: ! Pump Brand: Red Jacket <br /> Test Rate(gph): ' System,Type: Pressure <br /> Test Result: N/A <br /> !__.., _ _......_. _... .___.....__ Line Pressure(psi): 50 <br /> Line Start Time: 3:00 PM <br /> Test Method: ULLAGE Line End Time: 3:15 PM <br /> Line Start Level: 170 <br /> UllageVolume(gals.): I <br /> i Line End Level. -i50 <br /> j Ullage Test Time: <br /> Line Test Rate(gph): -0.021 <br /> Ullage Vacuum(psi): <br /> I Line Test Result: PASS <br /> i <br /> Ullage Result: N/A ' <br /> PSD <br /> 4 <br />