Laserfiche WebLink
UNDER DISPE SER CONTAINMENT C) TESTING <br /> Test Method By: O Manufacturer • Industry Standard o Professional Engr o Other(see below) <br /> Test Method Uses: O Pressure O Vacuum • Hydrostatic o Other(see below) <br /> Measuring Equipment Used: INCON TS-STS (Electronic Sump Test System) <br /> Description Disp# 1/2 Disp#3/4 Disp#5/6 <br /> UDC manufacturer Bravo Bravo Bravo <br /> UDC material FRP FRP FRP <br /> UDC depth (inches) 30 30 30 <br /> Height from UDC bottom to highest 11 11 11 <br /> piping penetration <br /> Height from UDC bottom to lowest 3 3 3 <br /> electrical penetration <br /> Condition of UDC prior to testing Dry Dry Dry <br /> Portion of UDC tested Entire Entire Entire <br /> Type of shut-down present Sensor Sensor Sensor <br /> Was sensor removed for testing? Yes Yes Yes <br /> Was sensor properly replaced after testing? Yes Yes Yes <br /> Depth of water level from UDC bottom (in.) 13 13 13 <br /> Wait time for water level to stabilize (hr:min) 0:05 0:05 0:05 <br /> Test start time 9:19 AM 9:48 AM 9:19 AM <br /> Initial Probe Reading 1.6846 3.6341 5.9304 <br /> Test end time 9:35 AM 10:03 AM 9:35 AM <br /> Final Probe Reading 1.6844 3.6344 5.9307 <br /> Test duration (hr:min) 0:16 0:15 0:16 <br /> Change in water level (t 0.0000 inches) -0.0002 0.0003 0.0003 <br /> Pass/Fail threshold (10.0020 inches/}Hr.) 0.0020 0.0020 0.0020 <br /> FTEST RESULT PASS PASS PASS <br /> Comments: <br /> 0 2006 Walton Engineering,Inc. <br />