Laserfiche WebLink
GARY PETERS ENTERPRISES <br /> 11300 COL OMA RD. B-7 <br /> RANCHO CORDOVA, CA. 95670 <br /> 916-638-7198 <br /> Date : 7-13-89 <br /> Ref . #890713 <br /> To: DAVE CASTRO <br /> U.C.L.L.N.L. <br /> P.O.BOX 808 L-193 <br /> LIVERMORE <br /> Test location : Tank #865-DIUI & 834-DIUI , Site 300 . <br /> On 7-13-89 testing was completedq using the Tank Audit LEAK <br /> COMPUTER in accordance with the precision test requirements of <br /> NFPA 329-1983 and Section 2643 of the California Underground Tank <br /> Regulations (Aug. 1985) . The criteria for acceptable tank <br /> integrity allowed by these documents is based upon a detection <br /> limit of 0 .05 gal/hr and a consideration of other variable <br /> factors. <br /> leak tank+ <br /> Tank gals. contents level rate tank pipes <br /> 865-DIUI 4000 Diesel 7" 0 .04 Pass Pass <br /> 834-DIUI 1000 Diesel a 2211 -10 .02 Pass Pass <br /> (gph) <br /> level in fill pipe , above tank top . <br /> A copy of the data is attached. <br /> Sinc y rel <br /> 'y <br /> GARY PET ENT. <br />