GARY PETERS ENTERPRISES <br /> 11309 COL OMA RD. B-7 <br /> RANCHO CORDOVAj CA. 95670 <br /> 916-638-7198 <br /> Dates 5-23-89 <br /> Ref . #890523 <br /> To: DAVE CASTRO <br /> U.C.L.L&N.L. <br /> P .O.BOX 808 L-193 <br /> LIVERMORE <br /> Test location : Tank #801-R2UI9 Site 300 . <br /> On 5-23-89 testing was completed, using the Tank Audit LEAK <br /> COMPUTER in accordance with the precision test requirements of <br /> NFPA 329-1983 and Section 2643 of the California Underground Tank <br /> Regulations (Aug. 1985) . The criteria for acceptable tank <br /> integrity allowed by these documents is based upon a detection <br /> limit of 0 .95 gal/hr and a consideration of other variable <br /> factors. <br /> leak tank+ <br /> Tank gals. contents level rate tank pipes <br /> 80I-R2U1 4000 waste water * 050 2.87 # # <br /> *.250 0.01 pass pass <br /> (gph) <br /> level in riser , above tank top <br /> # results inconclusive <br /> A copy of the data is attached. <br /> Sincerely <br /> OVARY PETE ENT. <br />