Laserfiche WebLink
GARY PETERS ENTERPRISES <br /> 11300 COLOMA RD. 8-7 <br /> RANCHO CORDOVA, CA. 95570 <br /> 916-638-7198 <br /> Date : 6-14-88 <br /> Ref . #: 880614GP <br /> To: DAVE CASTRO <br /> U.C.L.L .N.L. <br /> P .O .BOX 808 L-193 <br /> LIVERMORE <br /> Test. location : TANK #836-41D (SITE 300) , #424-41D (LIVERMORE) . <br /> On 6-14-88 testing was completed, using the Tank Audit LEAK <br /> COMPUTER in accordance with the precision test requirements of <br /> NFPA 329-1983 and Section 2643 of the California Underground Tank <br /> Regulations (Aug. 1985) . The criteria for acceptable tank <br /> integrity allowed by these documents is based upon a detection <br /> limit of 0 .05 gaI/hr and a consideration of other variable <br /> factors . <br /> leak tank+ <br /> Tank gals. contents level rate tank pipes <br /> 836-41D 280 DIESEL * 21 " 0 .80 PASS PASS <br /> 424-41D 300 DIESEL + 27" -.81 PASS PASS <br /> (GPH) <br /> * LEVEL IN STAND PIPE ABOVE GROUND LEVEL. <br /> + LEVEL IN FILL PIPE ABOVE TANK TOP . <br /> A, copy of the data is attached. <br /> Sincerely IE <br /> GARY ERS ENT. <br />