Laserfiche WebLink
GARY PETERS ENTERPRISES <br /> 11300 COLOMA RD. B-7 <br /> RANCHO CORDOVA, CA. 95670 <br /> 916-638-7198 <br /> Date : 6-2-88 <br /> Ref . #: 880602GP <br /> To: DAVE CASTRO <br /> U.C.L .L.N.L. <br /> P.O .BOX 808 L-193 <br /> LIVERMORE <br /> Test location : TANK #834-11D (SITE 300) , #435-11D (LIVERMORE) . <br /> On 6-2-88 testing was completed, using the Tank Audit LEAK <br /> COMPUTER in accordance with the precision test requirements of <br /> NFPA 329-1983 and Section 2643 of the California Underground Tank <br /> Regulations (Aug. 1985) . The criteria for acceptable tank <br /> integrity allowed by these documents is based upon a detection <br /> limit of 0 . 05 gal/hr and a consideration of other variable <br /> factors. <br /> leak tank+ <br /> Tank gals. contents level rate tank pipes <br /> 834-IID 1000 DIESEL * 22" -.01 PASS PASS <br /> 435-IID 280 DIESEL * 15" 0 .00 PASS PASS <br /> (GPH) <br /> *LEVEL IN FILL PIPE, ABOVE TANK TOP . <br /> A copy of the data is attached. <br /> Sincerely <br /> GARY PET ENT. <br />