Laserfiche WebLink
` <br /> GARY PETERS ENTERPRISES <br /> 11300 Coloma Road , B-7 <br /> Rancho Cordova, California 95670 <br /> ( 916) 638-7198 <br /> Date : 07/19/87 <br /> Ref # ; 8707183P <br /> DAVE CASTRO <br /> U. C . L . L .N . L. <br /> P . O . BOX 808 L-193 <br /> LIVERMORE , CA. 94550 <br /> Dear DAVE CASTRO : <br /> We tested the storage tank( s) at LAWRENCE LIVERMORE LAB , <br /> SITE 300 , TANK#879-11G & 879-126, on 07/18/87 using the <br /> TanK Audit LEAK COMPUTER in accordance with the precision <br /> test requirements of WFPA 329-1983 and Section 2643 of <br /> the California Underground Tank Regulations (Aug, 1985) . <br /> The criteria for acceptable tank integrity allowed <br /> by these documents is based upon a detection limit of <br /> 0 .05 gal /hr and a consideration of other variable factors. <br /> The results of the tests are given below and indi - <br /> cate whether the tanks and/or piping passed or failed the <br /> integrity criteria . Any piping that was tested only in- <br /> cluded that Ahich is attached to the tank up to a pump <br /> or a cneck/contrcl val ve . The test level at which the <br /> tank and pip | ng passed s given in inches above the top <br /> of the tank . <br /> Tank Tank and Tank <br /> <-ga}-> ` ^ � <br /> 18000 REG. PASS @ O . 00GPH PASS <br /> 10000 UNL. PASS z 0 .03GPH PASS <br /> A copy of the data is attached . <br /> Sincerely , <br /> GARY PETERS ENTERPRISES <br /> -- Enc � osures <br /> [ � <br />