Laserfiche WebLink
GARY PETERS ENTERPRISES <br /> • 11300 Coloma Road, B-7 <br /> Rancho Cordova, California 95670 <br /> (916) 638-7198 <br /> Date : 11/06/86 <br /> Ref #: 861104GP <br /> PO*104,603 <br /> RICK HENRY <br /> LAWRENCE LIVERMORE LAB <br /> P.O.BOX 808 L-193 <br /> LIVERMORE, CA . 94550 <br /> Dear RICK HENRY: <br /> We tested the storage tank ( s) at LA1,,JRENCE LIVERMORE LAB , <br /> LIVERMORE-SITE 300 , LIVERMORE, on 11:'04:'x'6 using the <br /> Tank Audit LEAK COMPUTER in accordance with the precision <br /> test requirements of NFPA 329-1983 and Section 2643 of <br /> the California Underground Tank Regulations (Aug, 1985) . <br /> The criteria for acceptable tank integrity allowed <br /> by these documents is based upon a detection limit of <br /> 0 .05 gal/hr and a consideration of other variable factors. <br /> • The results of the tests are given below and indi - <br /> cate whether the tanks and/or piping passed or failed the <br /> integrity criteria. Any piping that was tested only in- <br /> cluded that which is attached to the tank up to a pump <br /> or a check./control valve . The test level at which the <br /> tank and piping passed is given in inches above_ the top <br /> of the tank . <br /> Tank Tank and Tank <br /> (gal ) Grade Piping oni >. <br /> 3000 DIESEL FAIL aZ 17 PASS <br /> 350 DIESEL PASS Z 11 PASS <br /> A copy of the data is attached. <br /> Sincerely, <br /> GAR`( PETERS ENT RPRISES <br /> B. <br /> i <br /> • Enclosures <br />