Laserfiche WebLink
10- <br /> AFFILIAT0 <br /> Thornton Environmental Construction,, InC. LPLE Ij <br /> P.O. Box 360833 Milpitas, CA 95036-0833 <br /> Phone(408) 946-1015 • (209) 834-0792 9 Fax(209) 834-0795 <br /> ANNUAL TEST RESULTS FOR THE PRODUCT AND VAPOR OVERFELL CONTAINMENT <br /> Name: Lawrence Livermore National Laboratory Date: 9-21-2005 <br /> Address: Site 300, Tracy, CA 95376 Bldg: 882 <br /> Test Method Developed By: ❑ Spill Bucket Manufacturer ®Industry Standard ❑Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ®Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used: Caldwell Systems Sump Level Change Indicator Equipment Resolution: 0.0025" <br /> Spill Box# Spill Box# Spill Box# Spill Box# <br /> 882-D1U1 <br /> Nominal Bucket Capacity in 7 Gallons <br /> gallons: <br /> Test fails if the bucket does Pass <br /> not hold at least 5 gallons <br /> Bucket Depth(inside 15" <br /> measurement): <br /> Wait time between filling with 5 Minutes <br /> water and starting test: <br /> Test Start Time: 8:48a <br /> Initial Reading(R): 10.25" <br /> Test End Time: 9:08a <br /> Final Reading(RF): 10.25" <br /> Test Duration: 20 Minutes <br /> Change in Reading(RF-N: 0.00" <br /> Pass/Fail Threshold/Criteria: 0.00" <br /> Test Result: I W'Pass ❑Fail; ❑Pass ❑Fail El Pass ❑Fail 13 Pass ❑Fail <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> Test water was disposed of by LLNL. <br /> Technician Name: Brian Thornton Signature: /� <br />