10/01/2009 20:14 FAX 925 422 2748 WGMG [mol l/011 <br />I 1 0 0 <br />r <br />Thornton Environmental Construction,-UPLEIj <br />P.O. Box 360833 Milpitas, CA 95036-0833 <br />Phone (408) 946+1015 * (209) 834-0792 * Fax (209) 83 4-0795 <br />Name: Lawrence Livermore National Laboratn <br />Date- 9-21-2009 <br />Address: Site 300, Trac , CA 95376 <br />Bldg: 882 <br />Tea Method Developed By: <br />El spin Budod mawfim"M <br />MbWusuy S=dard a Professional Fmgb= <br />E3 Other fspec!&) <br />Test Method Used: <br />®H 'c <br />13 Other (Spwtfy) <br />Test Fqwpment Used: Caldwell Systems Sump Level ChwW lndtca= <br />4T!hpant ResoIuIiow.O..002Y' <br />is <br />I C I. I <br />Box 0 SPjH VQx # <br />Spin Box # spin BU # <br />882-DlUl <br />Nominal Bucket Capacity in <br />5 Gallons <br />gallons* <br />Test faUs if the bucket does <br />Pass <br />not hold at least 5 rAtons <br />Bucke(Mpth (inside <br />15 - <br />Wait time wtwem fiumg with <br />5 minutes <br />I vMu and starting test; <br />Test SWI Time: <br />9-44a <br />Initial Reading (Ril: <br />14.25" <br />Test End Time: <br />10,05a <br />Final Reading (RF): <br />14,25" <br />Test Duration: <br />21 minutes <br />Change in Reading (Rp-�; <br />0.001, <br />Pass/Fail Threshold Criteria: <br />O.W" <br />;EA <br />P <br />U IF <br />0 Pin 0 FAR 9 Pas It FAR Q rMs U tiffi 13 Pm U f9t <br />❑. <br />Comm eats — (rviude in <br />fonnation on repairs made prior to tesdng, and recommended fbIIo%-Wfor failed tests) <br />Drain valve was removed anci clearted, then wAtsMIled in order to pass. <br />Test water was disposed of by LLNL- <br />Technician Name- Brian Thornton <br />