Laserfiche WebLink
E <br />(Attachment C). Based on this information we have determined that this is a Vapor <br />Recovery system. <br />Based on this determination. Chapter 10 of NFPA 30A would be the guiding section (see <br />Attachment A). This chapter addresses both Vapor Processing and Vapor Recovery <br />systems. The 20 foot separation requirement (section 10. 1.6 as noted above) applies to <br />the Vapor Processing System part of this Chapter. <br />As this is a Vapor Recovery System the requirements would be in section 10.2 (see <br />Attachment A). There is no separation requirement in this section of the code. The <br />proposed installation location meets the requirements of the applicable section of the <br />code. <br />After your review if you have any questions or would care to discuss any item further <br />please contact Michael Jones, phone 925-423-8691, E -Mail jones161@llnl.gov. <br />C, K4X 240A/� <br />'-Approved: 0 <br />John A. Sharry <br />Fire Marshal <br />Subject Matter Expert <br />Emergency Management Department <br />Attachments: <br />"rwml, #J <br />I'MeT171 =I- W=, <br />Michael L. Jones <br />Fire Protection Engineer <br />Emergency Management Department <br />A. Excerpts from NFPA 30A — Code for Motor Fuel Dispensing Facilities and Repair <br />Garages <br />B. Office of the State Fire Marshal Certification <br />C. Underwriters Laboratories Certification <br />Cc: <br />Mecozzi, Jim <br />L-373 <br />Pindea, Jose <br />L-695 <br />Ocampo, Bev <br />L-373 <br />Schwartz, Bill <br />L-627 <br />Sharry, John <br />L-388 <br />Zalk, David <br />L-871 <br />Team I Files <br />EMD Files <br />