Laserfiche WebLink
AFFILIATE <br />(TfO <br />Thornton Environmental Construction,, Inc. E� EM � <br />P.O. Box 360833 Milpitas, CA 95036-0833 <br />Phone (408) 946-1015 • (209) 834-0792 . Fax (209) 834-0795 <br />ANNUAL TEST RESULTS FOR THE PRODUCT AND VAPOR OVERFILL CONTAINMENT <br />Name: Lawrence Livermore National Laboratory <br />Date: 9-19-2008 <br />Address: Site 300, Tracy, CA 95376 <br />Bldg: 879 <br />Test Method Developed By: <br />0 Spill Bucket Manufacturer <br />ElIndustry Standard ❑ Professional Engineer <br />❑ Other (Specifi ) <br />Test Method Used: <br />© Hydrostatic <br />❑ Other (Sped fv) <br />Test Equipment Used: Visual test <br />Equipment Resolution: 0.0625" <br />Spill Bos # Spill Boa # <br />Spill Box # Spill Bos # <br />879-G3U1 <br />Nominal Bucket Capacity in <br />5 Gallons <br />gallons: <br />Test fails if the bucket does <br />Pass— <br />not hold at least 5 gallons <br />— <br />Bucket Depth (inside <br />12.5" <br />measurement): <br />Wait time between filling with <br />5 Minutes <br />water and starting test: <br />Test Start Time: <br />10:15a <br />Initial Reading (Rj): <br />11.4375" <br />Test End Time: <br />11:15 <br />Final Reading (RF): <br />11.4375-- <br />1.=1375"Test <br />TestDuration: <br />l Minutes <br />Change in Reading (RF-Rj): <br />0.00" <br />Pass/Fail Threshold / Criteria: <br />0.00" <br />Test Result: <br />© Pass ❑ Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />❑ Pass O Fail <br />Comments — (include information on repairs made prior to testing, and rrecomneeiided follow-up,for failed tests) <br />This report reflects a retest of 879-G3U1 spill bucket after replacement of the fill cap. <br />Test water was disposed of by LLNL. <br />Technician Name: Brian Thornton Signature:�3 /---� <br />