Laserfiche WebLink
r <br />AF FILIATC <br />Thornton Environmental Construction Inc. 'Fels- <br />P.O. Box 360833 Milpitas, CA 95036-0833 <br />Phone (408) 946-1015 * (209) 834-0792 9 Fax (209) 834-0795 <br />ANNUAL TEST RESULTS FOR THE PRODUCT AND VAPOR OVERFILL CONTAINMENT <br />Name: Lawrence Livermore National Laboratory <br />Date: 9-8-2008 <br />Address: Site 300, Tracy, CA 95376 <br />Bldg: 882 <br />Test Method Developed By: <br />❑ Spill Bucket Manufacturer !]Industry Standard <br />❑ Professional Engineer <br />❑ Other (Specify) <br />Test Method Used: <br />IZI Hydrostatic <br />❑ Other (Sped fid) <br />Test Equipment Used: Caldwell Systems Sump Level Change Indicator <br />E ui ment Resolution: 0.0025" <br />Spill Box # Spill Box # Spill Box # <br />Spill Box # <br />882-DlU1 <br />Nominal Bucket Capacity in <br />Gallons <br />gallons: <br />Test fails if the bucket does <br />Pass <br />not hold at least 5 gallons <br />Bucket Depth (inside <br />15" <br />measurement): <br />Wait time between filling with <br />5 Minutes <br />water and starting test: <br />Test Start Time: <br />9-38a <br />Initial Reading (R): <br />14.50" <br />Test End Time: <br />9:58a <br />Final Reading (RF): <br />14.50" <br />Test Duration: <br />20 Minutes <br />Change in Reading (RF -RI): <br />0.00' <br />Pass/Fail Threshold / Criteria: <br />0.00" <br />Test Result: <br />1M Pass ❑ Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />Test water was disposed of by LLNL. <br />Technician Name: Brian Thornton <br />