Laserfiche WebLink
AFFILIATE <br /> i Inc. PCI <br /> Thornton Environmental Construction,, <br /> P.O. Box 360833 Milpitas, CA 95036-0833 <br /> Phone(408) 946-1015 • (209)834-0792 9 Fax (209) 834-0795 <br /> ANNUAL TEST RESULTS FOR THE PRODUCT AND VAPOR OVERFILL CONTAINMENT <br /> Name: Lawrence Livermore National Laboratory Date: 8-08-2012 <br /> Address: Site 300, Tracy, CA 95376 Bldg: 879 <br /> Test Method Developed By: ❑Spill Bucket Manufacturer OO Industry Standard ❑Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ©Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used: Visual <br /> uiment Resolution: 0.0625" <br /> Spill Box# Spill Box# Spill Boa# Spill Boz# <br /> 879-G3U1 879-D1U1 <br /> Nominal Bucket Capacity in 5 Gallons 7 Gallons <br /> gallons: <br /> Test fails if the bucket does pass Pass <br /> not hold at least 5 gallons <br /> Bucket Depth(inside 12.50" 16.50" <br /> measurement): <br /> Wait time between filling with 5 minutes 5 minutes <br /> water and starting test: <br /> Test Start Time: 11:12a 11:10a <br /> Initial Reading A): 11.50" 16.00" <br /> Test End Time: 12:12p 12:10p <br /> Final Reading(RF): 11.50" 16.00" <br /> Test Duration: 60 minutes 60 minutes <br /> Change in Reading(RF-RI): 0.00GPH 0.00GPH <br /> Pass/Fail Threshold/Criteria: 0.10GPH 0.10GPH <br /> Test Result: m Pass ❑Fail ©Pass ❑Fail Q Pass Ll Fail ❑Pass ❑Fail <br /> Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> Test water was disposed of by LLNL. <br /> Technician Name: Brian Thornton Signature: <br />