Laserfiche WebLink
AFFILIATE <br /> tTU <br /> W Thornton Environmental Construction Inc. PCI <br /> P.O. Box 360833 Milpitas, CA 95036-0833 <br /> Phone(408)946-1015 • (209)834-0792 •Fax(209) 834-0795 <br /> ANNUAL TEST RESULTS FOR THE PRODUCT AND VAPOR OVERFILL CONTAINMENT <br /> Name: Lawrence Livermore National Laboratory Date: 8-02-2011 <br /> Address: Site 300, Tracy, CA 95376 Bldg: 882 <br /> Test Method Developed By: 0 Spill Bucket Manufacturer ®Industry Standard ❑Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ©Hydrostatic <br /> D Other(Spec) <br /> Test Equipment Used: Caldwell Systems Sump Level Change Indicator <br /> Equipment Resolution: 0.0025" <br /> Spill Boz# Spill Boz# Spill Bos# Spill Bos# <br /> 882-DlU1 <br /> Nominal Bucket Capacity in 7.5 Gallons <br /> gallons: <br /> Test fails if the bucket does Pass <br /> not hold at least 5 gallons <br /> Bucket Depth(inside 15" <br /> measurement): <br /> Wait time between filling with 5 minutes <br /> water and starting test: <br /> Test Start Time: 9:45a <br /> Initial Reading M): 14.25" <br /> Test End Time: 10:35a <br /> Final Reading(RF): 14.25" <br /> Test Duration: 50 minutes <br /> Change in Reading(RF-Rj): 0.00GPH <br /> Pass/Fail Threshold/Criteria: 0.10GPH <br /> Test Result: 181 Pass ❑Fail ©Pass ©Fail Ll Pass O Fail E3 Pass O Fail <br /> Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> Test water was disposed of by LLNL. <br /> Technician Name: Brian Thornton Signature:'= --------- <br />