Laserfiche WebLink
E <br />'A 2� "O'� <br />, D <br />PEL <br />GEW Thornton Environmental Consticticr,,nc.ercrixsr <br />P.O. Box 360833 Mlpitas, CA 95036-0833 <br />A, 11111 — — I V95 <br />Name: Lawrence Livermore National Laboratory Date: 8-01-2017 <br />Address: Site 300, Tracy, CA 95376 Bldg: 882 <br />Test Method Developed By: LJ Spill Bucket Manufacturer ®Industry Standard L3 Professional Engineer <br />U Other (Specify) <br />Test Method Used: 0 Hydrostatic <br />L3 Other (Specify) <br />Test Equipment Used: Caldwell Sump Level Change Indicator <br />Spill Box # I Spill Box # <br />882-TFUD01 I <br />Resolution: 0.0025" <br />Spill Box # I Spill Box # <br />Nominal Bucket Capacity in <br />gallons: <br />7.5 Gallons <br />Test fails if the bucket does <br />not hold at least 5 gallons <br />Pass <br />Bucket Depth (inside <br />measurement): <br />15" <br />Wait time between filling with <br />water and starting test: <br />5 minutes <br />Test Start Time: <br />9:25a <br />Initial Reading (RI): <br />14.75" <br />Test End Time: <br />9:52a <br />Final Reading (RF): <br />14.75" <br />Test Duration: <br />27 minutes <br />Change in Reading (RF-Rj): <br />0.00, <br />Pass/Fail Threshold / Criteria: <br />-0. 10gph <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />Test water was disposed of by LLNL. <br />Technician Name: Brian Thornton <br />