Laserfiche WebLink
EIM"" <br />Thornton Environmental Constructi(*�]Ihc. <br />E RMY 91 -VM 9 —Va OR 9 -11 T W T ff , � � � � � � � IZI!111 553 60 1 A. I Do 111111il - 1 1 �i <br />Name: Lawrence Livermore National Laboratory Date: 8-01-2017 <br />Address: Site 300, Tracy, CA 95376 Bldg: 879 <br />Test Method Developed By: <br />L3 Spill Bucket Manufacturer ®Industry Standard 0 Professional Engineer <br />LI Other (Specify) <br />Test Method Used: <br />0 Hydrostatic <br />LI Other (Specify) <br />Test Equipment Used: Caldwell Sump Level Change IndicatorI Euip!aent Resolution: 0.0025" <br />- <br />Spill Box # <br />879-TFUG01 <br />Spill Box # <br />879 -TFUD01 <br />Spill Box # <br />Spill Box # <br />Nominal Bucket Capacity in <br />gallons: <br />5 Gallons <br />5 Gallons <br />Test fails if the bucket does <br />not hold at least 5 gallons <br />Pass <br />Pass <br />Bucket Depth (inside <br />measurement): <br />12.50" <br />12.75" <br />Wait time between filling with <br />water and starting test: <br />5 minutes <br />5 minutes <br />Test Start Time: <br />10:17a <br />11:50a <br />Initial Reading (Rj): <br />12.25" <br />12.50" <br />Test End Time: <br />10:42a <br />12:18p <br />Final Reading (RF): <br />12.25" <br />12.50' <br />Test Duration: <br />25 minutes <br />28 minutes <br />Change in Reading (RF -RI): <br />0.001, <br />0.001, <br />Pass/Fail Threshold Criteria: <br />-0. 10gph <br />-0. 10gph <br />Test Result: <br />IS) pass 1 0 Fail <br />Ml Pass U Fail <br />LI Pan U Fail <br />Ll Pass < U Fag <br />— Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />Test water was disposed of by LLNL. <br />Technician Name: Brian Thornton Signature: <br />