Laserfiche WebLink
4 <br /> 440 10"µrd _. <br /> *OTANK, INC. <br /> **** CERTIFICATE OF UNDERGROUND STORAGE TANK INTEGRITY **** <br /> PRECISION VOLUMETRIC QUANTITATIVE LEAK TEST <br /> The following underground storage tank system has been tested and is <br /> certified TIGHT at: <br /> STATION NUMBER TANK NUMBER TANK CONTENTS TANK CAPACITY <br /> 827-DlU1 827-DlUl DIESEL FUEL 10000.000 <br /> TANK LOCATION: LAWRENCE LIVERMORE NATIONAL LABORATORY <br /> P.O. BOX 808-L-663 <br /> LIVERMORE, CA 94550 <br /> TANK OWNER: LAWRENCE LIVERMORE NATIONAL LABORATORY <br /> PROTANK, INC. is authorized to test and certify this <br /> tank by the: STATE OF CALIFORNIA <br /> This CERTIFICATION meets the requirements and guidelines of applicable State <br /> and local regulations as well as National Fire Protection Association NFPA <br /> Title 329, 40 CFR 280.43(c) , and 40 CFR 280.44(b) . <br /> Certification Date : 1-21-94 <br /> Test Results Certified by : RAY MOALEMAN (92-1364 ) <br /> Recertification Date Recommended : 1-21-95 / <br /> p t <br /> PROTANK II�C� JRATED`( P� ETARY) <br /> System Accuracy (Standard Tank): 0.059ph =Pd>0.95/Pfa<0.05; 0.10gph = Pd>0.99/Pfa<0.01 <br /> PROTANK INCORPORATED 417 Paseo de la Playa Redondo Beach, California 90277 (310)378-0818 <br />