Laserfiche WebLink
Western Operations <br /> 1252 Quarry Laney"" 1> 1�( "Al-TitClayton <br /> P.O. Box 9019 ( i <br /> Pleasanton,CA 94566 " <br /> ENVIRONMENTAL <br /> Fax (510)426-0106 DLEC p M : 17 CONSULTANTS <br /> November 11, 1993 <br /> Mr. David Castro <br /> LAWRENCE LIVERMORE NATIONAL LABORATORY <br /> P.O. Box 808, L-633 <br /> Livermore, California 94550 <br /> Clayton Project No. 38641.00 <br /> Subject: Tank Integrity Testing Results <br /> Dear Mr. Castro: <br /> Clayton Environmental Consultants, Inc. is pleased to report the results and <br /> observations of the tank integrity tests recently completed at: <br /> Lawrence Livermore National Laboratory <br /> Site 300 <br /> Tracy, California <br /> The tank was tested on November 1, 1993, using the Homer EZY-CHEK tank testing <br /> system. <br /> The results of the tests are provided below. <br /> It <br /> N:;-,- <br /> .. ::>:::: :> <br /> »< <br /> 871-D1U1 2,000 Diesel High -0.0102 <br /> * GPH @ 95% confidence of <.1 as accepted by the State of California and the <br /> Environmental Protection Agency. <br /> The tank was shown to be "product tight." <br /> ENGWM1.0105 <br /> Clayton Environmental Consultants,Inc. - Detroit - New York/Newark - Atlanta - San Francisco - Los Angeles <br /> Honolulu - Windsor,ON • Toronto - Birmingham,U.K. - London,U.K. - Southampton,U.K. - Gateshead,U.K. <br />