Laserfiche WebLink
SWRCB,January 2002 Page 2 <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: F] Tank Manufacturer IX Industry Standard F-1 Professional Engineer <br /> El Other (Specify) <br /> Test Method Used: F] Pressure FRI Vacuum Hydrostatic <br /> 0 Other (Specify) <br /> Test Equipment Used: Equipment Resolution: <br /> Tank# 2 REG Tank# Tank# Tank# <br /> Is Tank Exempt From Testing? Yes X No El Yes No YesEl No Yes No <br /> Tank Capacity: 12,000 <br /> Tank Material: DW FIBERG <br /> Tank Manufacturer: unknown <br /> Product Stored: REGULAR. <br /> Wait time between applying <br /> pressure/vacuum/water and 5min <br /> starting test: <br /> Test Start Time: 8:46 <br /> Initial Reading(Ri): 10hg <br /> Test End Time: 9:46 <br /> Final Reading(RF ): 10hg <br /> Test Duration: 1hr <br /> Change in Reading(RF-I I ): 0 <br /> Pass/Fail Threshold or Criteria: 2hg <br /> Was sensor removed for testing? T- "NNA Ye N N Ye N NA Ye NNA <br /> Was sensor properly replaced and ❑ ❑ —I _I—Iverified functional after testing? X N NA Ye N NA Ye N NA Ye N NA <br /> Comments- (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> I Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23,Section 2637(a)(6)) <br />