Matrix of Nonmetallic Pipe Monitoring Applications
<br /> Gravity Flow, Vacuum (V), Pressure (P), and Interstitial Liquid Level Monitoring (ILLM)
<br /> (Enclosure to State Water Board letter dated February 29, 2008; Matrix Updated March 23, 2011)
<br /> MEN I MM
<br /> Secondary Containment FueW6 Open closed
<br /> Brand Type and Size (min.5 psi rating on SC per UQ (min.50 psi rating on SC per UQ
<br /> (Coaxial reported as ID of PS;
<br /> SOS reported as OD of SQ Gravity Flow or Vacuum,Pressure,or
<br /> Ambient ILLM Pressurized ILLM
<br /> Advantage Earth Products,Inc.
<br /> Electr-O-Fuze Flexible;Coaxial(coil); Black 11/2& 2" MV,CrHB,AM Gravity Flow V'P
<br /> Ameron
<br /> Dualoy 3000/L Rigid;SOS;3"&4" MVCTHBAM Gravity Flow V, P
<br /> Rigid; SOS;6" MV,CT-,HB,AM Gravity Flow None
<br /> Dualoy 3000/LC( Rigid;Coaxial(sticks);2"&3" MVCT,HB,AM Gravity Flow,AILLM' V,P,PILLM,
<br /> Rigid;Coaxial(sticks);4" MVCT,HB,AM Gravity Flow,AILLM' None
<br /> Franklin Fueling/APT
<br /> XP-150-Sc Flexible;Coaxial(coil); 11/2" MV,CTHBAM Gravity Flow V
<br /> XP-1001 175,200 Flexible-Coaxial(coil); I", IY4"1&2" MV CT HB AM Gravity Flow None
<br /> NUPI
<br /> Smartflex Flexible;Coaxial(coil); 2",21/2"1&S" MVCTHB,AM Gravity Flow V,P
<br /> Flexible;Coaxial(sticks); 2",4"&51, MV,CTHBAM Gravity Flow V,P
<br /> , ,
<br /> OPW-FCS
<br /> C15,C20,C30 Flexible;Coaxial(coil); 11/2",2"'&3" MV,AM Gravity Flow None
<br /> C75,C104 Flexible;Coaxial(colo; 3/4"&1" MV,AM Gravity Flow V,P
<br /> PGFC-21501 Flexible;Coaxial(coil); 11/2" MV,AM Gravity Flow V,P
<br /> PetroTechnik
<br /> UPP Flexible;Coaxial(coil); 11/2",2" MV,CrHB,AM Gravity Flow V,P
<br /> Flexible;Coaxial(sticks)' 11/2" 2" 3" 4" MV CT HB Gray! FlowV,P
<br /> NOV Fiber Glass Systems
<br /> Red Thread IIA Rigid;SOS;3"&4" MV,CrHB,AM Gravity Flow V,P
<br /> Rigid; SOS; 6" MV,CrHBAM Gravity Flow None
<br /> Western Fiberglass
<br /> Co-Flex Flexible;Coaxial(coil); 11/2" 2" &3" MV,AM Gravity Flow,AILLM2 None
<br /> Co_FleX4
<br /> Flexible;Coaxial(coil); 3/4"i I11 MV,AM Gravity Flow,AILLM2 V,P,PILLM'
<br /> Co-FlexI Flexible;Coaxial(coil); 11/2" MV,AM Gravity Flow,AILLM2 V, P,PILLMI
<br /> 1. Use only with Ameron's Brine Filled Interstitial Space Monitoring System(limited to maximum length of 344 feet).
<br /> 2. Use only with Westem Fiberglass Co-Flow Hydraulic Interstitial Monitoring System(limited to maximum length of 200 feet).
<br /> 3. Procedures to verify the appropriate pipe for V or P applications include Inspection in the field for a date stamp equal to or after November 30,2006,and a marking of"50 PSI"on
<br /> the secondary containment.
<br /> 4. Procedures to verify the appropriate pipe for V and P applications include Inspection in the field for a date stamp equal to or after January 29,2008 and a marking of 50 PSI"on the
<br /> secondary containment.
<br /> 5. Procedures to verify the appropriate pipe for V or P applications include inspection in the Field for a date stamp equal to or after November 16,2006,and a marking of"50 PSI"on
<br /> the secondary containment,
<br /> 6. E85 Is covered within the CT fuels testing range;therefore only pipe with the Cr fuels marking can store E85.